8.2.6.
Checking the automatic air vent
1. Switch off the boiler electrical power supply.
2. Close the main gas inlet valve.
3. Remove the front panel.
4. Tilt the control panel into the high position.
5. Remove the cover from the sealed chamber.
¼
see chapter: "Removing the cover from the sealed
6. If any leaks are detected, replace the air vent.
8.2.7.
Checking the safety valve
1. Check whether there is any water in the safety valve flow pipe.
2. If any leaks are detected, replace the safety valve.
8.2.8.
Checking the condensate trap
1. Remove the cover from the sealed chamber.
¼
see chapter: "Removing the cover from the sealed
2. Remove the condensate trap and clean it.
3. Fill the siphon with water.
4. Put the condensate trap back in place.
8. Checking and maintenance
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
80
22/04/2016 - 300026141-001-07