The Reliable Automatic Sprinkler Co., Inc.,
103 Fairview Park Drive, Elmsford, New York 10523
Model GFR
Model GFR Recessed
Quick Response
Sprinklers
Bulletin 131
Rev
.
J
Bulletin 131
Rev.
J
Model GFR Sprinkler Types
Standard Upright
Standard Pendent
Horizontal Sidewall
HSW1 Deflector
Intermediate Level Upright
Intermediate Level Pendent
Conventional
Model GFR Recessed
Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
HSW1 Deflector
Approvals
Underwriters Laboratories, Inc. (UL)
Underwriters’ Laboratories of Canada (ULC)
NYC BS&A No. 587-75-SA
.....
.....
MIL-S-901C and MIL-STD-167-1
NYC MEA 258-93-E
1.
2.
3.
4.
5.
6.
7.
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Product Description
Reliable Models GFR and GFR Recessed Sprinklers are
Quick Response fusible solder type automatic sprinklers.
These sprinklers have demonstrated response times in
laboratory tests which are five times faster than standard
response sprinklers.
This quick response enables the Models GFR and GFR
Recessed Sprinklers to apply water to a fire much faster
than standard response sprinklers of the same temperature
rating.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler spacing are in accordance with the latest
published standards of the National Fire Protection Associ-
ation or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for standard area cover-
age and standard water densities as specified in NFPA 13.
Quick response sprinklers and standard response sprin-
klers should not be intermixed.
Upright
Pendent
Intermediate Level
Upright
Intermediate Level
Pendent
Small Orifice
Upright
Conventional
Recessed
Horizontal Sidewall
HSW-1 Deflector
Horizontal Sidewall
HSW-1 Deflector
Recessed
Pendent
Recessed FP
Pendent