Error Causes and Remedies
TR-Electronic GmbH 2018, All Rights Reserved
Printed in the Federal Republic of Germany
Page 82 of 84
TR - ELA - BA - DGB - 0028 - 00
06/21/2018
8 Error Causes and Remedies
8.1 Optical displays
Assignment of the LEDs can be seen in chapter “Bus status display” on page 64.
POWERLINK
Status-LED
Cause
Remedies
ON (green)
All OK, the node is in a NMT
State Machine defined condition.
Normal operating state
ON (red)
POWERLINK error occurred
Try to restart the device: Voltage OFF/ON. If the
error arises repetitive, the measuring system
must be replaced.
ENCODER
Status-LED
Cause
Remedies
OFF
Voltage supply absent or too low
- Check voltage supply, wiring
- Is the voltage supply in the permissible range?
Hardware error, measuring
system defective
Replace measuring system
ON (green)
Measuring system ready for
operation
-
ON (red)
Measuring system error occurred
Try to restart the device: Voltage OFF/ON. If the
error arises repetitive, the measuring system
must be replaced.
Blinking (red)
Teach-in process active
finish the teach-in process
L/DA-LED
Cause
Remedies
OFF
No POWERLINK connection
Check bus cable
ON (green)
Measuring system ready for
operation, Ethernet connection
established.
-
Blinking (yellow)
Data transfer active.
-