Intelligent Room Controller/Sensor

English

Product programme

REH CT3   

Wired room controller with clock

REH DT3   

 Wired room sensor with temperature adjustment, mode switch 

(Auto, Day, Night, Frost Protection) and floor limit sensor

Mounting of room controller/sensor (figs 1 and 2)

The unit is used for comfort temperature control in rooms. The unit should 

be mounted on an internal wall approx. 1.4-1.7 metres above the floor in 

such a way as to allow free air circulation around it. Draughts and direct 

sunlight or other heat sources must be avoided.

Fig. 1 Removing the front cover

     BR 1026A02a

Fig. 2

     BR1026A01a

REH CT3 / REH DT3: Wired room controllers/sensors – bus connection 

(figs 3 and 4). 

Only REHAU units which are suitable for two-wire communication can be used. 

Standard installation cable of minimum 2 x 0.25 mm² can be used. Units can 

be connected in conventional star formation or in bus mode (daisy chain). The 

master has four sets of terminals marked SENSOR/CONTROLLER BUS that can be 

used for connecting the 2-core signal cable from the unit.

67337 02/15 (HKT)

• English

Any unit can be connected to any pair of terminals. The total length of the 2-wire 

system can be up to 300 m with a maximum length of 100 m between any two 

units. For further information see the table below.

Remember to c to + and – to – .

Table: Length of cable

Standard cable

Max cable length from 

Master to Room Controller/

Sensor with display

Max cable length from 

Master to Room Controller/

Sensor without display

≥0.25 mm²

Up to 100 m *

Up to 300 m

≥0.50 mm²

Up to 200 m *

Up to 300 m

≥0.75 mm²

Up to 300 m *

Up to 300 m

*) Up to 300m if operation without backlight is acceptable.

Fig. 3

     BR935A03A

Fig. 4

     BR935A03A