uREG User Manual
37
7.11.
PS -0/ SS-0 MODULE (SLOTS 3 & 6)
The
PS-0
p
ower
s
upply module is a switching power unit module dedicated to
u
REG
.
Each
u
REG
unit can be equipped with one or two PS-0 module(s) (installed in slot #3 and/or
#6). For a configuration with two PS-0 modules, each of them can be powered by separate
guaranteed voltage (the other module serves as “hot standby”).
Rated supply voltage
220 V DC (or 230 V AC)
Admissible range of supply voltage changes: AC
88 ÷ 365 VDC (100 ÷ 260VAC)
Power input at 220 V DC
<15 W (type 7W)
Undervoltage protective interlock threshold:
> 375 V DC
Overvoltage interlock hysteresis:
app. 12 VDC
In addition, the PS-0 module is equipped with:
3 unipolar digital inputs
→ terminals 8, 9, 10
;
2 make-contact relays (1 pair)
→ terminals 5, 6
;
switchable relay for handling the Alarm circuit
→ terminals 2, 3, 4
;
internal input of power unit efficiency control;
and (optionally)
switchable relay for resetting the Alarm circuit
→ terminal 1
(by means of an external contact-type logic system).
Terminals on the
PS-0
module are grouped into 2 slots:
3-pin MSTBA2.5/3-G strip (pitch: 5.00 mm, max 12 A, 250 V)
to apply auxiliary supply voltage and earthing;
11-pin MSTBA2.5/11-G strip (pitch: 5.00 mm, max 12 A, 250 V)
to handle inputs/outputs.
Fig. 7.11. Terminals of the PS-0 / SS-0 module.
CAUTION
For double power unit configurations (with hot standby), it is forbidden to replace the power unit module during
operation of the device! In order to replace a faulty module, disconnect auxiliary power completely for the time of
this action.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...