REGIS T-X-B – Access or time and attendance controller

 

 

 

 

 

10/2016 

Black line 

www.jantar.si 

 

 

 

 

 

 

 

                                         
 
 
 
 
 
        

 

REGIS T-X-B – ACCESS or TIME AND 
ATTENDANCE CONTROLLER 

 
The Regis is a controller with built-in proximity card reader and 7” 
LCD capacitive touch screen display. It is designed for residential 
and business buildings, offices, shops, etc. The controller can have 
125kHz or 13.56MHz reading frequency. 
The entire set-up procedure is carried out with the software. The 
controller allows access for up to 30000 users and saves 100000 
events. If you bought the controller in time and attendance kit, 
then inputs and outputs cannot be controlled. 
It can also be used as a Wiegand 26-bit reader, if needed. 
The SDK is also available for this controller. If a user or software 
producer wants to develop its own application, please contact us.  

 
TECHNICAL DATA 

REGIS T-X-B 

REGIS T-1-B reading frequency 

125kHz 

REGIS T-1-B reading distance 

Up to 15cm 

REGIS T-1-B current consumption in 
standby mode 

300mA 

REGIS T-1-B reading field in vertical 
position 

Bottom side of  
the controller 

REGIS T-1-B reading field in horizontal 
position 

Right side of the 
controller 

REGIS T-3-B reading frequency 

13.56MHz 

REGIS T-3-B reading distance 

Up to 7cm 

REGIS T-3-B current consumption in 
standby mode 

330mA 

REGIS T-3-B reading field in vertical 
position 

Bottom side of  
the controller 

REGIS T-3-B reading field in horizontal 
position 

Right side of the 
controller 

Dimensions (mm)  

210x150x35

 

 (WxHxD) 

Protection 

IP21 

Operating voltage 

From 9V to 14V DC 

Operating temperature 

From -20°C to 60°C 

Connector 

2x 8pin, 1x ethernet 

Display 

TFT - capacitive touch 

Tamper 

Accelerometer   

Display resolution 

1024 x 600 

Humidity 

10-80%, non condensing 

Memory  

30000 cards or codes 
100000 events 

Inputs 

Door status  
Push button 

Outputs 

Transistor output for el. strike 
0.5A  

Clock 

Real time clock, battery backup 
(max. ten hours) 

Communication 

RS485 
Ethernet 

Keypad 

Configurable buttons 
Selectable colors 

*if Regis T is in Spider mode, the same data applies 

 
 
 
 
 

 
Power supply 

The controller need’s external power supply to operate. The Spider 
W40 power supply is sufficient to power two controllers and two 
12V electric strikes or two 12V magnetic locks (0.5A). If you will 
use it as a standalone controller and low consumption electric 
strike (0.25A) you can use power supply Spider W5.  

 
Voltage drops and cable signal interferences

 

When you connect the controller, use cable with a diameter of at 
least 0.22mm

2

. If the cable length exceeds 25m, use one twisted 

pair of UTP cables for the positive (+) pole and one for the 
negative (-) pole. The cable length between power supply and the 
controller should not exceed 50m. 
Take into consideration that a 0.22mm

2

 cable has a resistance of 

approximately 9 ohm per 100m. The power supply at the end of 
cable should be a minimum of 9V. If you are using el. strike, it is 
highly recommended that the voltage drop is calculated. At greater 
distances, a thicker cable of 0.5mm

2

 or more should be used 

wherever possible. 
If the load is, for example, 0.5A (with el. strike) then, on the 
0.22mm

2

 cable voltage drop will be 4.5V at 100m. For the device 

with 60mA consumption, the voltage drop is 0.5V. 
 
Reading distance depends on where the controller is installed. The 
presence of metal or interferences can significantly reduce the 
reading distance.

 DO NOT 

install the controller directly on metal 

surfaces and/or cover it with a metal cover. 
It is 

not recommended

 to install controllers closer than 

30cm

 

from each other in any direction. Otherwise, it may result in 
inaccurate readings or, indeed, in the controller

 not reading at 

all

 

For the Regis T-3-B to comply with EMC directives (CE), you 
have to put ferrite core on the cable as close to the 
controller as possible, making two turns! 

 
 

CONNECTOR DESCRIPTION 

Connectors are marked on the housing 
with 1 in 2. First contact on both 
connectors starts on the marked side (1 
and 2) 

 
 

 
 

 

 

CONNECTOR 1 – connection of power supply, el. strike...  

Contact 

Description 

Specification 

1  

9-14V DC 

Power supply 

2  

GND 

Ground 

3  

El. strike output 

Max. 0,5A 
Active = GND 

4  

Alarm output 

Max. 0,5A 
Active = GND 

5  

Door status switch input 

Active = GND 

6  

Push button input  

Active = GND 

7  

CA 

RS485 A line 

8  

CB 

RS485 B line 

 
CONNECTOR 2 – connection of external reader  

Contact 

Description 

Specification 

1  

9-14V DC 

Power supply 

2  

GND 

Ground 

3  

Data 0 

Wiegand protocol 

4  

Data 1 

Wiegand protocol 

5  

Buzzer output 

Active = GND 

6  

LED output  

Active = GND 

7  

XA – for protocol reader 

RS485 XA line 

8  

XB – for protocol reader 

RS485 XB line 

 