The controller automatically adapts its control mode to suit the  
dynamics of the controlled object. 

• 

For rapid temperature changes, such as supply air control, TTC80F 
will act as a PI controller with a set P-band of 20 K and a set I-time of 
6 minutes.

• 

For slow temperature changes, such as room control, the controller 
will act as a P controller with a set P-band of 1.5 K.

External control signal

TTC80F can also be used for control with an external 0...10 V DC control 
signal from another controller.
Remove the wire strap between terminals 7 and 9 and connect the control 

signal as shown in figure 8.

   

0-10V DC in

Signal neutral

8 9

7

Remove 

wire

 
Figure 8: Wiring of external control signal

A control signal of 0 V will provide an output of 0 % and a control signal of 
10 V an output of 100 %. The minimum and maximum limitation functions 
are not active when using this control mode.

Start-up and fault finding

1.  Begin by ensuring that all wiring has been performed correctly. 

2.  Measure the resistance between terminals L1out - L2out,  

L1out - L3out and L2out -L3out: 
At 400 V line voltage: 5.8 

Ω 

<R <92 

3.  Switch on the supply voltage and turn the setpoint knob to its 

maximum value. The LED should be either continuously on, or pulse 

on/off with a progressively longer ontime so that it is eventually on 

continuously.  

4.  Turn the setpoint knob to its minimum value. The LED should either 

switch entirely off or pulse with a progressively shorter ontime so that 
it finally switches off completely. At a middle position of the propor

-

tional band (when the setpoint = the actual value), the pulsing of the 
LED will perfectly coincide with the controller pulsing current to the 
heater. The pulse cycle time is 6...60 seconds depending on the  
settings of the CT potentiometer. Use a clamp-on multimeter to 
ensure current is passing to the heater when the LED is lit.

Troubleshooting

1.  Disconnect all wiring to the external sensor and setpoint device 

(if any). Measure the resistance of the sensor and/or setpoint 
potentiometer separately. The resistance of the potentiometer 

varies 0...5 kΩ between its minimum and maximum settings. The 
sensor resistance varies 10 kΩ...15 kΩ between the minimum 
and maximum temperature range. I.e. a TG-K330 has 15 kΩ at 
0°C and 10 kΩ at 30°C. The resistance changes by 167 Ω/°C.

 

2.  Leave the sensor terminals disconnected. Set all switches to 

their downward positions. Switch the supply voltage on. 
The controller should provide full, unimpeded output and the 
LED should be lit. Use a clamp-on multimeter to ensure current 
is passing to the heater. 

If the LED is not lit and no current is flowing: Ensure that termi

-

nals L1in, L2in and L3in all have power. If they do, the controller 
is probably faulty. 

If the LED is lit but no current is flowing: Measure the heater 

resistance. If it is OK, the controller is probably faulty. 

3. 

Switch off the supply voltage and short-circuit sensor inputs 1 

and 4. Switch the supply voltage on again. 
The controller should now not provide any output at all. The LED 

should be switched off. Use a clamp-on multimeter to ensure no 

current is passing to the heater. 

If the LED is off but current is flowing to the heater, the controller 

is probably faulty. 
If the LED is lit: Recheck the short-circuiting of the sensor inputs. 
If it is OK, the controller is probably faulty. 

4.  If everything is correct up to this point, the controller and the 

sensor are OK. 

Shut off the supply voltage, remove the wire strap from the the 

sensor input terminals and reconnect the sensor(s) and external 
setpoint potentiometer (if any). Set the switches to their correct 
positions and switch the supply voltage back on.

Limitation sensor

Terminals 5 and 6. Polarity insensitive. Low voltage.
During room temperature control, the supply air temperature can be 
provided with a minimum or maximum limitation. The limitation sensor 
is placed in the supply air duct, after the heater. Switches 2 and 3 are 
used to set the desired function. The Min. and Max. potentiometers 
are used to set the desired limitation temperatures.

    

TG-K360

5 6

 
Figure 7: Wiring of a limitation sensor

 

NOTE:

 TG-K360 must be used.

Settings

Potentiometers

Setp.

  Setpoint 0...30°C.

Min

 

Minimum supply air temperature limit for room control with 

 

minimum limitation. 0...30°C

Max

 

Maximum supply air temperature limit for room control with 

 

maximum limitation. 20...60°C.

CT

 

Pulse period. 6...60 seconds.

Switches

1

 

Down = Using external setpoint potentiometer

 

Up = Using integrated setpoint potentiometer

2

 

Down = Minimum limitation deactivated

 

Up = Minimum limitation active

3

 

Down = Maximum limitation deactivated

 

Up = Maximum limintation active

NOTE: 

The minimum and maximum limitation functions 

can be used separetely or at the same time.

Control principle

• 

TTC80F pulses the entire load On-Off. 

• 

The controller will adjust the mean power output to the current 

power demand by proportionally adjusting the On-time and Off-

time ratio.  

• 

The pulse period (= the total sum of the On-time and Off-time) is 

settable 6...60 seconds by using the potentiometer.

• 

TTC80F uses zero phase-angle firing to eliminate radio 

 

frequency interference.

Summary of Contents for TTC80F

Page 1: ...oltage 5 A Protection class IP20 Ambient temp 0 40 C non condensing Installation Mount TTC80F on a DIN rail in a cabinet or other casing Mount the controller vertically with the text right side up NOT...

Page 2: ...ull unimpeded output and the LED should be lit Use a clamp on multimeter to ensure current is passing to the heater If the LED is not lit and no current is flowing Ensure that termi nals L1in L2in and...

Page 3: ...de symmetriska Y kopplade v rmare och symmetriska eller osymmetriska Delta kopplade v rmare Regulatorn r endast avsedd f r elv rmestyrning Reglerprincipen g r att den inte kan anv ndas till motor elle...

Page 4: ...v ndas f r styrning med extern 0 10 V DC styrsignal fr n annan regulator Avl gsna bygeln mellan plintarna 7 och 9 och koppla in styrsignalen enligt figur 8 7 0 10V DC in Signalnoll 8 9 Avl gsna bygeln...

Page 5: ...ills r regulatorn och givare OK Sl av matningssp nningen ta bort kortslutningsbygeln fr n givaring ngarna och koppla in givare och eventuell yttre b rv rdes potentiometer terst ll funktionsomkopplarna...

Page 6: ...t von 6 Minuten Bei langsamen Temperaturver nderungen z B bei der Raumtemperaturregelung funktioniert er als P Regler mit einem festen Proportionalbereich von 1 5 K Externes Stellsignal TTC80F kann au...

Page 7: ...tiometer wieder an falls vorhanden Setzen Sie die Schalter in die korrekte Position und schalten Sie die Stromversorgung wieder ein INSTRUCTION i Veuillez lire cette instruction avant de proc der l i...

Page 8: ...choisir la fonction souhait e Les limites de temp rature souhait es sont indiqu es avec les potentiom tres Min et Max TG K360 5 6 Sch ma 7 Raccordement d une sonde de limite NOTE La sonde TG K360 doi...

Page 9: ...e consigne individuellement La r sistance du potentiom tre varie entre 0 5k entre les positions min et max La r sistance de la sonde varie entre 10k et 15k entre les temp ratures min et max dans la pl...

Reviews: