Regin TTC25X Instruction Manual Download Page 1

INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

TTC25X

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

TTC25X

Triac controller for proportional control 

of electric heating

TTC25X is a proportional controller for electric heating with automatic 
voltage adaption. TTC25X pulses the whole load On - Off. The ratio 
between On-time and Off-time is varied 0 - 100% to suit the prevailing 
heat demand. The current is always switched at zero phase angle to 
prevent RFI.
TTC25X can control both symmetrical Y-connected 3-phase heaters 
and symmetrical or asymmetrical Delta-connected heaters.
TTC25X is only intended for electric heating control. The control prin-
ciple makes it unsuitable for motor- or lighting control.
TTC25X is intended for DIN-rail mounting.

Control principle

TTC25X pulses the full load On - Off. TTC25X adjusts the mean 
power output to the prevailing power demand by proportionally adjust-
ing the ratio between On-time and Off-time.  

The cycle time (=the sum of On-time and Off-time) is adjustable 6...60 
seconds.

TTC25X has zero phase-angle firing to eliminate RFI.

Installation

Mount TTC25X on a DIN-rail in a cabinet or other enclosure.
Mount TTC25X vertically with the text right side up.
Protection class    

IP20.

Ambient temperature 

0...40°C

N.B. 

TTC25X emits approx. 45W of heat at full output which must be 

dissipated.

Wiring

Supply voltage

Terminals L1in, L2in and L3in. 
Supply voltage: 210...255 or 380...415V AC, 3 phase, 50...60 Hz with 
automatic voltage adaption. Maximum current 25A/phase.

   

11

3

L1 L2 L3 L3 L2 L1

8 9

 
Figure 1: Wiring of supply voltage and load

N.B. 

The supply voltage to TTC25X should be wired via an all-pole switch 

with a minimum contact gap of 3mm.

N.B. 

TTC25X must be earthed.

Load

Terminals L1out, L2out and L3out. Resistive 3-phase heater without 
neutral.  
Maximum load: 3300W/phase at 230V phase - phase voltage. 5750W/
phase at 400V phase - phase voltage.  
Minimum load: 530W/phase at 230V phase - phase voltage. 920W/phase 
at 400V phase - phase voltage.

Control signal

Terminals 8 and 9.
Terminal 8 = Signal neutral.
Terminal 9 = 0...10V DC.
0V input signal will give 0% output and 10V input will give 100% output. 

1778F

 

MAR 14

EN

   

 

    Figure 2: Wiring of control signal

NOTE:

 Do not leave the input unconnected since an open circuit will 

not give 0% output but approx. 50%. To ensure 0% output when no 
control signal is connected, the control input should be short-circuited.

Settings

CT Cycle time. 6...60 seconds. The sum of one On-period and one 
Off-period.

Start-up and fault finding

1. Check that all wiring is correct. Make sure the supply voltage is 
switched off.
 2. Measure the resistance between terminals L1out - L2out, 
L1out - L3out and L2out -L3out: At 230V phase-phase voltage: 
10.6

<R<64

. At 400V phase-phase voltage: 18.4

<R<115

.

3. Connect supply voltage and set the input signal to 10V DC. The 
LED on the TTC25X should be continuously on. Set the control signal 
to 0V DC. The LED should be continuously off. At intermediate posi-
tions the LED will pulse On-Off as the TTC25X pulses current to the 
heater. The pulse cycle period is approx. 6...60 seconds depending 
on the setting of the CT-potentiometer. Check with a clamp-on am-

meter that current is flowing to the heater.

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low  
Voltage Directive (LVD) 2006/95/EC through product standard 
EN 60730-1.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms with the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]