Regin TTC25 Instruction Download Page 2

TTC25

2

For slow temperature changes i. e. room control TTC25 will act as a P 
controller with a proportional band of 1.5K.

External control signal

TTC25 can also be run against a 0 - 10V DC control signal from another 
controller.
Remove the wire strap between terminals 7 and 9 and connect the control 

signal as shown in figure 8.

    

0-10V DC in

Signal neutral

8 9

7

Remove 

wire

 

Figure 8: Wiring of external control signal

0V input signal will give 0% output and 10V input will give 100% output. 
Minimum and maximum limit functions are not active when using an 
external control signal.

Start-up and fault finding

1.  Check that all wiring is correct and that the sensor selector switches 

are in the correct position. 

2.  Measure the resistance between terminals L1out - L2out, L1out - 

L3out and L2out -L3out:  
At 230V phase-phase voltage: 10.6

<R<66.4

.  

At 400V phase-phase voltage: 18.4

<R<115

3.  Connect supply voltage and turn the setpoint knob to the maximum 

value. The LED on the TTC25 should be continuously on or pulse 
on/off with longer and longer ontime and eventually be continu-
ously on.Turn the setpoint to the minimum value. The LED should 
be continuously off or pulse on/off with longer and longer offtime 
and eventually be continuously off. At a certain position (within the 
proportional band) the LED will pulse On-Off as the TTC25 pulses 
current to the heater. The pulse cycle period is approx. 6 -60 sec-
onds depending on the setting of the CT-potentiometer. Check with a 

clamp-on ammeter that current is flowing to the heater.

Something wrong?

1.  Remove wiring to external sensor (and setpoint if any). Measure the 

resistance of the sensor and setpoint separately

The potentiometer 

resistance varies 0-  5k

Ω 

between the lower and upper end-point. 

The sensor resistance varies between 10k

 and 15k

 between 

the upper and lower ends of the sensor temperature range. I.e. a 

TG-K330 has 15k

 at 0°C and 10k

 at 30°C. The resistance 

changes by 167

/°C. 

2.  Leave the sensor terminals unconnected. Set all switches in the 

downward position. Switch the voltage on. 
TTC25 should give full uninterrupted power and the LED should 

be lit. Check with a clamp-on ammeter that current is flowing to 

the heater. 

If the LED is not lit and no current is flowing: Check that you 

have power on terminals L1in, L2in and L3in and recheck the 
positions of the sensor selector switches. If OK the TTC25 is 
probably faulty. 

If the LED lights up but no current is flowing: Recheck the heater 

resistance as above. If OK the TTC25 is probably faulty. 

3.  Shut off power and short-circuit the sensor input 1 and 4. Switch 

on power again. 
TTC25 should not give out any power at all and the LED should 
be extinguished. Check with a clamp-on ammeter that no current 

is flowing to the heater.

 

If the LED is extinguished but current is flowing to the heater the 

TTC25 is faulty. 
If the LED is lit, recheck the shorting of the sensor input termi-
nals. If OK the TTC25 is faulty. 

4.  If everything is OK this far the TTC25 and the sensor/setpoint 

are OK. Shut off power, remove the wire strap from the the 
sensor input terminals and reconnect external sensor(s) (and 
setpoint if any).Set the switches to their correct positions. Con-
nect power.

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low Volt-
age Directive (LVD) 2006/95/EC through product standard EN 60730-
1.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms with the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

Limiting sensor

Terminals 5 and 6. Low voltage. Not polarity sensitive.
When running room temperature control the supply air temperature 
can be limited to a maximum and/or a minimum. The limiting sensor is 
placed in the supply air duct after the heater.
Choice of function is made using switches 2 and 3. Choice of limiting 
temperatures is made on potentiometers Min and Max.

    

TG-K360

5 6

 
Figure 7: Wiring of limiting sensor

 

N.B.

 As limiting sensor TG-K360 must be used.

Settings

Potentiometers

Setp.  Setpoint 0 - 30°C.
Min 

Minimum limit for supply air temperature when running room  

 

temperature control.

Max 

Maximum limit for supply air temperature when running room  

 

temperature control.

CT 

Cycle time. 6 - 60 seconds.

Switches

Down = External setpoint in use.

 

Up = Internal setpoint in use.

Down = Minimum limit not active.

 

Up = Minimum limit active.

Down = Maximum limit not active.

 

Up = Maximum limit active.

N.B. 

Minimum and maximum limiting functions may be used  

separately or at the same time.

Control principle

TTC25 pulses the full load On - Off. TTC25 adjusts the mean power 
output to the prevailing power demand by proportionally adjusting the 
ratio between On-time and Off-time. The cycle time (=the sum of On-
time and Off-time) is adjustable 0 - 60 seconds.

TTC25 has zero phase-angle firing to eliminate RFI.

TTC25 automatically adapts its control mode to suit the dynamics of 
the control object .
For rapid temperature changes i. e. supply air control TTC25 will act 
as a PI controller with a proportional band of 20K and a reset time of 
6 minutes.

Summary of Contents for TTC25

Page 1: ...phase 50 60 Hz with automatic voltage adaption Maximum current 25A phase N B The supply voltage to TTC25 should be wired via an all pole switch with a minimum contact gap of 3mm N B TTC25 must be ear...

Page 2: ...e sensor input 1 and 4 Switch on power again TTC25 should not give out any power at all and the LED should be extinguished Check with a clamp on ammeter that no current is flowing to the heater If the...

Page 3: ...med brytavst nd 3mm OBS TTC25 skall jordas 1 1 1 3 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Figur 1 Inkoppling av matningssp nning och belastning Belastning Plint L1ut L2ut och L3ut Resistiv 3 fas v rmare ut...

Page 4: ...kontinuerligt sl ckt I ett mellanl ge d rv rdet b rv rdet kommer lysdioden att blinka i takt med att TTC25 pulsar fram str m Pulscykeltiden r 6 60 sek beroende p inst llningen p CT potentiometern Kont...

Page 5: ...asse IP20 Umgebungstemperatur 0 40 C Beachte Der TTC25 erzeugt ca 45W Abw rme die abgef hrt werden mu Verdrahtung Versorgungsspannung Klemmen L1in L2in und L3in Versorgungsspg 210 255 oder 380 415V AC...

Page 6: ...durchgeschalten wird Die Pulszykluszeit liegt bei ca 6 60sec je nach Einstellung des CT Potis Testen Sie mit einem Zangenamperemeter ob der Strom auch durch die Last flie t Fehlersuche 1 Entfernen Sie...

Page 7: ...3 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Fig 1 Raccordement de la tension d alimentation et de la charge NOTE le TTC25 doit tre raccord la terre Charge Bornes L1ut L2ut et L3ut R chauffeur r sistif triphas...

Page 8: ...ce connect e Le TTC25 adapte la puissance moyenne la puissance souhait e en faisant varier progressivement la longueur des impulsions La p riode de r p tition des impulsions somme des temps aux niveau...

Reviews: