INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

TTC25

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

TTC25

Triac controller for proportional control 

of electric heating

TTC25 is a proportional controller for electric heating with automatic 
voltage adaption. TTC25 pulses the whole load On - Off. The ratio 
between On-time and Off-time is varied 0 - 100% to suit the prevailing 
heat demand. The current is always switched at zero phase angle to 
prevent RFI.
TTC25 can control both symmetrical Y-connected 3-phase heaters 
and symmetrical or asymmetrical Delta-connected heaters.
TTC25 is only intended for electric heating control. The control  
principle makes it unsuitable for motor- or lighting control.
TTC25 is intended for DIN-rail mounting.

Installation

Mount TTC25 on a DIN-rail in a cabinet or other enclosure.
Mount TTC25 vertically with the text right side up.
Protection class:    

IP20.

Ambien temperature: 

0 - 40°C

N.B. 

TTC25 emits approx. 45W of heat at full output which must be  

dissipated.

Wiring

Supply voltage

Terminals L1in, L2in and L3in. 
Supply voltage:   210-255 or 380-415V AC  
 

 

3 phase, 50 - 60 Hz with automatic voltage adaption.

 

 

Maximum current 25A/phase.

N.B. 

The supply voltage to TTC25 should be wired via an all-pole switch 

with a minimum contact gap of 3mm.

N.B. 

TTC25 must be earthed.

    

1

11

3

2 3 4 5 6 7 8 9

L1 L2 L3 L3 L2 L1

 
Figure 1: Wiring of supply voltage and load

Load

Terminals L1out, L2out and L3out.
Resistive 3-phase heater without neutral.
Maximum load: 

3300W/phase at 230V phase - phase voltage  (25A). 

 

 

5750W/phase at 400V phase - phase voltage (25A).

Minimum load: 

530W/phase at 230V phase - phase voltage (4A). 

 

 

920W/phase at 400V phase - phase voltage  (4A).

Main sensor and external setpoint (figs 2-6)

Terminals 1 and 4. Low voltage. Not polarity sensitive.

N.B. 

Terminals 2 and 3 are internally connected and are used to simplify 

wiring when using external setpoint.

N.B. 

Choice of internal or external setpoint is made  using switch 1.

1777F

 

FEB 14

EN

1 2

TG-K3xx

TG-G1xx

3 4

1 2

3

2

TG-K3xx

TG-G1xx

TG-R4xx

3 4

1 2

2

1

TG-K3xx

TG-G1xx

TBI-xx

3 4

Figure 6: Wiring of external, separate sensor when using 
potentiometer TBI-xx as external setpoint

Figure 2: Wiring of room sensor TG-R530 or TG-R6xx 
when using internal setpoint

Figure 3: Wiring of room sensor TG-R430 used as external 
setpoint and sensor

Figure 4: Wiring of floor or duct sensor when using 

internal setpoint

Figure 5: Wiring of external separate sensor when using TG-R4xx 
as external setpoint

1 2

2

1

TG-R5xx

TG-R3xx

3 4

1 2

3

1

TG-R4xx

3 4

Summary of Contents for TTC25

Page 1: ...phase 50 60 Hz with automatic voltage adaption Maximum current 25A phase N B The supply voltage to TTC25 should be wired via an all pole switch with a minimum contact gap of 3mm N B TTC25 must be ear...

Page 2: ...e sensor input 1 and 4 Switch on power again TTC25 should not give out any power at all and the LED should be extinguished Check with a clamp on ammeter that no current is flowing to the heater If the...

Page 3: ...med brytavst nd 3mm OBS TTC25 skall jordas 1 1 1 3 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Figur 1 Inkoppling av matningssp nning och belastning Belastning Plint L1ut L2ut och L3ut Resistiv 3 fas v rmare ut...

Page 4: ...kontinuerligt sl ckt I ett mellanl ge d rv rdet b rv rdet kommer lysdioden att blinka i takt med att TTC25 pulsar fram str m Pulscykeltiden r 6 60 sek beroende p inst llningen p CT potentiometern Kont...

Page 5: ...asse IP20 Umgebungstemperatur 0 40 C Beachte Der TTC25 erzeugt ca 45W Abw rme die abgef hrt werden mu Verdrahtung Versorgungsspannung Klemmen L1in L2in und L3in Versorgungsspg 210 255 oder 380 415V AC...

Page 6: ...durchgeschalten wird Die Pulszykluszeit liegt bei ca 6 60sec je nach Einstellung des CT Potis Testen Sie mit einem Zangenamperemeter ob der Strom auch durch die Last flie t Fehlersuche 1 Entfernen Sie...

Page 7: ...3 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Fig 1 Raccordement de la tension d alimentation et de la charge NOTE le TTC25 doit tre raccord la terre Charge Bornes L1ut L2ut et L3ut R chauffeur r sistif triphas...

Page 8: ...ce connect e Le TTC25 adapte la puissance moyenne la puissance souhait e en faisant varier progressivement la longueur des impulsions La p riode de r p tition des impulsions somme des temps aux niveau...

Reviews: