background image

INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

TRT5(D)-420

1

12864D

 

MA

Y 19

TRT5(D)-420

Temperature transmitters

TRT5-420 and TRT5D-420 are wall mounted room transmitters for 

temperature measurement.

Installation

The transmitter should be mounted in a location with good air circula-

tion where it can be expected to give a representative reading. It may 

be mounted on a wall-box or directly on the wall. 

To remove the front cover, press the locking tounge in the lower part of 

the casing using a 3 mm flat-blade screwdriver (see arrow in the figure 

below). Press and twist the screwdriver and at the same time pull the 

bottom part of the front outwards. When the bottom end of the front 

is free from the bottom part of the casing, slide the cover towards the 

top of the casing to free the hooks holding the upper edge of the front 

cover.
To select the temperature scale °C or °F, set dip-switch 4 as shown in 

the figure below.

Wiring

power supply

28 V > U

v

 > 11 + 0,02 x R

L

R

L

 ≤ 500 Ohm

Wiring for TRT5(D)-420

Technical data

Output signal

4...20 mA (T=0…50°C)

Supply voltage

Max. 28 V DC, min. 11+(0.02xR

L

) V DC

Power consumption

0.6 W

DC power supply

Min. 1W

Temperature range

0...50°C

Accuracy, temperature

±0.5°C at 20 °C

Protection class

IP30

Dimensions

100 x 85 x 30.5 mm

 

This product carries the CE mark.  

For more information, see www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontols.com, [email protected]