background image

INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

SDD-OE65-RACM

1

SDD-OE65-RACM

Optical smoke detector for duct mounting

SDD-OE65-RACM is an optical smoke detector with 24 V AC supply 

voltage for smoke detection in ventilation systems. The detector has 

a relay output for smoke alarm indication as well as a built-in auxiliary 

fan. SDD-OE65-RACM is not to be connected to Regin’s control units 

ABV...

Technical data

Supply voltage 

 

24 V AC ±15 %

Installation

Make a 30 mm hole at a suitable location on the duct. The detec-
tor should be mounted at least 3 duct diameters away from bends, 
air intakes or other sources of disturbance to the airflow in the duct. 
Remove the enclosure lid and remove the detector head which is 
bayonet mounted.
Mount the venturi tube by removing the screw from the tube’s 
unclosed end, stick the end of the tube into the hole in the bottom of 
the enclosure with the holes in the tube aligned with the enclosure’s 
longitudinal axis. Fasten the screw through the hole in the PC-board. 
Replace the detector head. To shorten the venturi tube remove the 
endplate and gasket from the tube’s outer end, shorten the tube mak-

ing sure to cut it at right angles and remount gasket and plate.
Temporarily replace the lid oriented so that the LED on the detector head 
is visible through the window. Put the tube through the hole in the duct, 
orient the unit so that the arrows on the lid point in the flow direction (see 
figure 1) and fasten the unit to the duct using the mounting ”wings”. For 
round ducts the wings can be bent to fit the duct curvature. For insulated 
ducts, special mounting brackets are available as an extra accessory.

Flow

Figure 1. Flow direction

Wiring

Wire the detector according to figure 2.
Terminal 1  

24 V AC ±15 % supply voltage

Terminal 2  

24 V AC ±15 % supply voltage

Auxiliary fan

Terminal 3  

24 V AC ±15 %

Terminal 4  

24 V AC ±15 %

Alarm relay

2 A, 24 V AC, potential-free change-over 
Terminal 6  

Normally closed

Terminal 7  

Common

Terminal 8  

Normally open

SDD-OE65-

RAC(M)

1
2
3
4

6
7
8

Figure 2. Wiring. Relay drawn in alarm position.

Function indicators

Flow indicator

The detector has a built-in flow indicator with a red signal flag which is 
located on the air inlet. During normal operation, it will be lifted by the 
flow of air, thereby indicating correct air flow through the detector.

Smoke alarm

The detector head has a built-in LED for alarm indication. The LED is 
normally extinguished but will light up red at a smoke alarm. Simulta-
neously the alarm relay is activated.

Function test

The cover has a red plastic plug on the side of the lid to simplify 
control with e.g. test gas. Avoid spraying gas directly onto the detector 
head and only use small amounts at a time to avoid unnecessary 
contamination of the detector.

Auxiliary fan

When the air handling unit is stopped, the fan is normally activated in 
order for SDD-OE65-RACM to detect smoke in the air duct.

Maintenance

The detector should be tested and cleaned on a yearly basis to 
ensure proper function. Cleaning of the venturi tubes, the housing and 
the outside of the detector head can be done using a vacuum cleaner. 
Note: Do not try to disassemble the detector head for cleaning.

EMC emissions and immunity standard

The product conforms with the requirements of European EMC 
standards CENELEC EN50081-1 and EN50082-1 and carries the CE 
mark.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regin.se, [email protected]

8485A

 

JUN 1

1

EN

Reviews: