Regin RVASN08 Instructions Download Page 2

  

  

Rotational direction settings

Two DIP switches, used to set the rotational direction of the actuator, 
are located under the cover. To change from counter-clockwise to 
clockwise direction, the DIP switches (A) must be properly set.

   

A

B

ON

1 2

ON

1 2

It is important never to reverse the polarity of the plug (B), as 
this will result in the actuator not functioning properly.

Manual override

To manually set the valve position, first hold down the clutch button 

on the side of the actuator. This enables turning the lever attached to 
the position indication arrow to the desired valve position.
The actuator will return to its automatic function when the clutch but-
ton is released.

   

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low 
Voltage Directive (LVD) 2006/95/EC through product standards 
EN 60730-1:2011.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 
2004/108/EC through product standards EN 55014-1 and  
EN 55014-2.

RoHS

This product conforms to the Directive 2011/65/EU of the European  
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]

Ventilställdon för 0...10 V-styrning

RVASN08 är avsedd att användas tillsammans med Regins tryckober-
oende ventiler PCMTV32-50.

Tekniska data

Matningsspänning  

24 V AC, 50/60 Hz / 24 V DC  

 

 

±20 % (2-punkt och 3-punkt),  

 

 

230 V AC, 50/60 Hz (0...10 V DC)

Effektförbrukning 
     RVASN08-24   

3,9 W (0,4 W/6,5 VA i standbyläge) 

     RVASN08-24A   

4,8 W (1,2 W/6,5 VA i standbyläge) 

     RVASN08-230   

4,8 W (1,2 W/6,5 VA i standbyläge)

Max. slaglängd (rotation)  

0...90º

Ställtid  

 

30 s/90º

Vridmoment  

 

8 Nm

Vinkelbegränsning  

5...85º (i inkrement om 5º)

Omgivningstemperatur  

-20...+50°C

Max. medietemperatur  

120°C

Lagringstemperatur  

-40…+70°C

Omgivande luftfuktighet  

5...95 % RH

Skyddsklass  

 

IP54

Montering

Ventilen ska monteras så att ställdonet hamnar med drivstången inom 90° 
från lodlinjen med motorhuset överst. Ventilställdonets drivstång ska vara 
i sitt centrerade läge vid montering på ventilen. 

   

90º

90º

2

i

Läs denna instruktion innan produkten 

monteras och ansluts

INSTRUKTION

 

RVASN08