INSTRUCTION
i
Read this instruction before installation
and wiring of the product
Valve actuator for 0...10 V control
RVASM16 is intended for use together with Regin’s pressure inde-
pendent PCMTV32-50 valves.
Technical data
Supply voltage
24 V AC, 50/60 Hz / 24 V DC
±20 % (2-position and 3-position),
230 V AC, 50/60 Hz (0...10 V DC)
Power consumption
3.9 W (0.4 W/6.5 VA in standby)
Max. stroke (rotation)
0...90º
Stroke time
80 s/90º
Torque
16 Nm
Angle limitation
5...85º (in increments of 5º)
Ambient temperature
-20...+50°C
Max. media temperature
120°C
Storage temperature
-40…+70°C
Ambient humidity
5…95 % RH
Protection class
IP54
Mounting
The valve should be mounted so that the actuator drive rod is within 90°
from the vertical line and the motor housing is on top. The drive rod of the
valve actuator should be centered when it is mounted on the valve.
90º
90º
Mounting of actuator
without an adapter
Wiring
The actuator has terminals for connection. Depending on the actuator
model (24 V AC or 230 V AC), the wiring will differ slightly:
12
3
S
~
+
12
3
S
~
-
+ -
2-position (On/Off)
3-position
┷
-
+
~
0 (2)...10 V
0(4)...20 mA
0 (2)...10 V
24 V AC/DC
0...10 V
Function
The actuator is intended for control, opening and closing of rotating
model PCMTV32-50 valves. The actuator is equipped with position
indication in the form of a graded scale on its cover.
Rotational direction settings
Two DIP switches, used to set the rotational direction of the actuator,
are located under the cover. To change from counter-clockwise to
clockwise direction, the DIP switches (A) must be properly set.
A
B
ON
1 2
ON
1 2
It is important never to reverse the polarity of the plug (B), as
this will result in the actuator not functioning properly.
RVASM16
11805B JUL
15
EN
1
DIP switches
Mounting of actuator
with an adapter
Summary of Contents for RVASM16