RVAR5-24A
SW1 Operational direction of the valve
On: The valve is closed when the stem is in its lowest position.
Off: The valve is closed when the stem is in its highest position.
SW2 Flow characteristics
On: Gives linear flow characteristics in combination with equal
percentage valves. The actuator moves logarithmically in relation
to the control signal.
Off: Unchanged valve characteristics. The actuator moves linearly in
relation to the control signal.
SW3 Control signal
On: 2...10 V DC
Off: 0...10 V DC
The actuator can also be connected to a 4...20 mA control signal.
In this case, a 500 Ohm resistor should be installed between the
control signal input (terminal 3) and system neutral (terminal 2)
and SW3 should be set to position On (2...10 V DC).
The control signal will then be converted to 2...10 V DC.
SW4 Reverse/Direct operation
On: Reverse operation. The actuator closes the valve on increasing
control signal.
Off: Direct operation. The actuator opens the valve on increasing
control signal.
SW5 Split function
On: Split function. Two actuators can share a control signal and work
in sequence.
Off: No split function.
SW6 Working range when using split function
On: 5…10 V= 0…100 % (6…10 V when SW3=On)
Off: 0…5 V= 0…100 % (2…6 V when SW3=On)
LEDs
The actuator has two LEDs with indications according to the table
below.
Indication
Green steady light
Actuator working properly
Green light quick flashing
Test run in progress
Green light slow flashing
The setting was changed during the
operation. The new setting will be
valid after the next power on.
Red and green steady light
End position reached
Red light slow flashing
Override input mode
Operation faulty, either the improper
installation or the valve stroke lost
Red light quick flashing
Manual override mode
2
This product carries the CE-mark. More information is available at www.
regincontrols.com.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]
i
Läs denna instruktion innan produkten
monteras och ansluts
INSTRUKTION
RVAR5-24A
Ventilställdon för 0(2)...10 V-styrning
RVAR5-24A är ett ventilställdon för styrning av MMV- och MMR-
ventiler. Ställdonet har automatisk lyfthöjdsjustering och kan köras
manuellt.
Tekniska data
Matningsspänning
24 V AC ±15 %, 50/60 Hz
eller 24 V DC ±15 %
Styrsignal
0(2)…10 V DC
Max. effektförbrukning
5,1 W / 13,9 VA
Slaglängd
10…30 mm
Ställtid
1,5 s/mm
Ställkraft
500 N
Omgivningstemperatur 0…50ºC
Lagringstemperatur -40…80°C
Omgivande luftfuktighet
10…90 % RH
Mått
150 x 295 x 85 mm
Skyddsklass
IP54
Montering
Om ventilens spindeladapter och ventilhalsadapter inte redan är mon-
terade på ventilen, montera dem. Dra ut ventilspindeln så långt det
går. Montera spindelanslutningen och fixera den med muttern.
Ta bort U-bulten från ställdonets ok. För in ventilspindeln i oket och se
till att spindeladaptern passar i hålet i det vinklade järnet på ställdonets
drivspindel.
Spåret i ventilhalsadaptern måste vara i linje med monteringshålen
för U-bulten på ställdonet. Om spindeln behöver flyttas in eller ut för
att detta ska ske, tryck ned mittenknappen på manöverratten och
vrid denna medurs för att flytta ut spindeln, och moturs för att flytta in
spindeln (se Manuell överstyrning). För in U-bulten när ventilen är i rätt
läge. Dra åt muttrarna tills ventilen sitter stadigt fast.
Nedmontering i omvänd ordning.
SV