Regin RVAR5-24A Instruction Download Page 1

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAR5-24A

Valve actuator for 0(2)...10 V control

RVAR5-24A is a valve actuator designed for control of MMV and MMR 

valves. The actuator has automatic self stroke adjustment and can be 

operated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

  

or 24 V DC ±15 %

Control signal 

 

0(2)…10 V DC 

Max. power consumption  5.1 W / 13.9 VA 
Stroke 

 

10…30 mm 

Stroke time 

 

1.5 s/mm 

Force 

 

500 N 

Ambient temperature 

0…50°C 

Storage temperature 

-40…80°C 

Ambient humidity   

10…90 % RH 

Dimensions (WxHxD) 

150 x 295 x 85 mm 

Protection class   

IP54

Installation

If the valve stem adaptor and valve throat adaptor are not already mounted 

on the valve, mount them. Pull the valve stem out as far as possible. 

Mount the stem connector and fix it with the nut. 

Remove the locking bolt (U-bolt) from the actuator yoke. Insert the valve 

stem into the yoke and make sure that the stem adaptor engages the hole 

in the angled iron of the actuator drive spindle.

The groove in the valve throat adaptor must be made to line up with the 

U-bolt mounting holes on the actuator. If the spindle needs moving in or 

out for this to happen, depress the central part of the manual button and 

turn it clockwise for the actuator spindle to extend, and anti-clockwise for it 

to retract (see Manual override). When the valve is in the correct position, 

insert the U-bolt. Tighten the bolt nuts until the valve is firmly gripped. 

Disassembly in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and end position calibration

Stroke and end position calibration is not necessary due to a construction 

utilizing end position stops. When the valve reaches the end position, a 

force is generated.

 Once the force of the actuator reaches a predefined 

level, the limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are six DIP switches for setting different functions. Follow the 

table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

1 (On)

0 (Off)

SW1

Spindle down when the 
valve is closed

Spindle up when the valve 
is closed (FS=factory set-
ting)

SW2

LOG

LIN (FS)

SW3

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW4

Reverse operation

Direct operation (FS)

SW5

Y signal split in accordance 
with the setting of SW6

No split function (FS)

SW6

5(6)...10 V = 0...100 %

0(2)...5(6) V = 0...100 % 
(FS)

RVAR5-24A

7058M

 

MA

Y 18

EN

1

Summary of Contents for RVAR5-24A

Page 1: ...Control signal from controller U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and end position calibration Stroke and end position calibration is not necessa...

Page 2: ...tion reached Red light slow flashing Override input mode Operation faulty either the improper installation or the valve stroke lost Red light quick flashing Manual override mode 2 This product carries...

Page 3: ...Direkt verkan FI SW5 Y signalsplit enligt inst ll ning av SW6 Ingen splitfunktion FI SW6 5 6 10 V 0 100 0 2 5 6 V 0 100 FI SW1 Ventilens arbetsriktning On Ventilen r st ngd n r spindeln r i sitt nedr...

Page 4: ...estigen B gelschraube U B gel vom Joch des Stellantriebs abnehmen und Ventilspindel in das Joch einf hren Dabei sicherstellen dass der Spindeladapter im Loch der Kupplung an der Antriebsstange einrast...

Page 5: ...Stellantrieb f hrt logarithmisch bezogen auf das Stellsignal Off Unver nderte Durchflusscharakteristik Der Stellantrieb f hrt linear bezogen auf das Stellsignal SW3 Stellsignal On 2 10 V DC Off 0 10 V...

Page 6: ...ctions pr c dentes dans l ordre inverse Positions de montage 90 90 Raccordement 24 V AC DC 1 2 3 4 5 1 2 3 4 5 6 Y 0 2 10 V DC U 0 10 V DC Signal neutre Signal de commande du r gulateur Tension de mes...

Page 7: ...est alors converti en un signal 2 10 V DC SW4 Course directe invers e On Action invers e L actionneur ferme la vanne quand le signal de commande augmente Off Fonctionnement direct L actionneur ouvre...

Reviews: