Regin RVAR5-230 Instruction Download Page 1

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAR5-230

Valve actuator for 3-position control

RVAR5-230 fits valve series MMV/MMR. The actuator can be set 
manually.

Technical data

Supply voltage 

 

230 V AC ±15 %, 50 Hz

 

Control signal 

 

3-position

 

Power consumption 

Max. 12 W

 

Stroke 

 

10...30 mm

 

Stroke time 

 

3 s/mm

 

Force  

 

500 N

 

Ambient temperature 

0...50ºC

 

Storage temperature 

-40...80°C

 

Ambient humidity   

10...90 % RH

 

Dimensions 

 

200 x 310 x 135 mm

 

Protection class   

IP54

Mounting

If the valve stem lock and valve throat adaptor are not already 
mounted on the valve, mount them. Pull the valve stem out as far as 

possible. 
Remove the locking bolts and U-bolt from the actuator yoke.
Depress the spring-loaded tab on the drive rod coupling device and fit the 
valve stem into the coupling. Release the tab to connect the valve to the 
actuator.
The position of the yoke on the valve stem adaptor must be adjusted so 
that the U-bolt mounting holes line up with the groove in the valve throat 
adaptor. If the drive rod needs to be moved in or out for this, depress the 
central button of the control knob and turn it clockwise to extend the drive 
rod and counter-clockwise to retract it (see Manual override).
Mount the U-bolt and the nuts. Tighten the nuts until the actuator is firmly 
attached. Disassembly takes place in reverse order.

Mounting positions

   

90º

90º

Wiring

1

2

3

Y1

N

Y2

L      N

230V AC

Y1 circuit closed = Actuator spindle

is extending from the actuator
Y2 circuit closed = Actuator spindle

is retracting into the actuator

Calibration

Field calibration is not required. When the valve reaches an end position 
and the actuator provides nominal positioning force, power to the actuator 

motor is cut automatically.

Manual override

To manually set the valve position, first depress the central part of the 
knob until it clicks in place and remains depressed (1 in the figure). 
The valve position may then be changed manually by turning the 
knob (2 in the figure). Clockwise rotation will extend the drive rod and 
anti-clockwise rotation will retract it. 
To return to normal operation, position the knob so that it is in line with 
the text (Auto) on the cover. Then press down on the outer parts of 
the knob (3 in the figure). The depressed central part will pop out and 
the actuator will return to operation.

 

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low Volt

-

age Directive (LVD) 2006/95/EC through product standards EN60730-
1:2000 and EN60730-2-14:1997.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 
2004/108/EC through product standards EN60730-1:2000 and 
EN60730-2-14:1997.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden

 

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50

 

www.regin.se, [email protected]

RVAR5-230

10329A

 

MA

Y 13

EN

1