Regin RVAPC-24A Instruction Manual Download Page 1

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

Valve actuator for 0...10 V control

RVAPC-24A is intended to be used together with Regin’s pressure 
independent valves PCTV, PCTMV and PCTVS DN15-32.

Technical data

Supply voltage 

 

24 V AC/DC ±15 %, 50...60 Hz 

Control signal 

Proportional 0...10 V

Power consumption  

1.5 W / 2.5 VA

Max stroke 

 

6 mm / 3.2 mm

Stroke time  

 

8 s/mm

Force  

 

120 N +30 % -20 %

Ambient temperature, operation   0…50°C
Max media temperature 

95°C

Storage temperature  

-20…+65°C

Ambient humidity    

Max. 95 % RH

Measurements (W x H x L) 

40 x 79.5 x 80 mm 

Protection class   

IP43

Adapters*
   for valves with 2.7 mm stroke  VA7010
   for valves with 6 mm stroke 

VA748X

*Must be ordered separately.

Mounting

The valve should be mounted so that the drive rod on the actuator is 

within 90° from the vertical line and the motor housing is on top. The valve 

actuator’s drive rod should be in its highest/innermost position when it is 

mounted on the valve. 

Fix the actuator to the valve using the connection nut and the correspond-

ing adapter (must be ordered separately)

, manual power is sufficient.

For valves with 2.7 mm stroke, the actuator needs to be set in 3.2 mm 

stroke mode. For valves with 6 mm stroke, the actuator needs to be set in 

6.3 mm stroke mode.

90º

90º

Wiring

The actuator has a connection cable with a connector which is intended 
for connection to the bottom of the actuator. There is only one way to plug 
in the contact. Be careful not to damage the cable if the connector needs 
to be removed from the actuator.

Blue = system neutral (-)
Red = 24 V (+))
Grey = control signal

BLK

(-)

(+)

AC

24 V

...10 V

Function

When the actuator is first turned on it will run a complete cycle to self-

calibrate. The stem extends to the max end stroke in order to get the 
zero point before it moves back to the position corresponding to the 
control signal.
When the signal increases (e.g. from 0 to 10 V) the stem will extend 
if the actuator is set to direct action (DA, DIP switch 4 is in position 
OFF) and retract if it set to reverse action (RA, DIP switch 4 is in 
position ON). When the signal decreases, the stem will retreat if the 
actuator is set to DA and extend if it is set to RA.
NB: PCTV, PCMTV and PCTVS DN15-32 valves are normally open. 
They close when the actuator stem extends.
If the signal stays at 100 %, the actuator will start every 2 hours and 
try to move the stem in the corresponding direction for 60 s to check 
that the end stroke has been reached. 

Position and status indication

RVAPC-24A has a two-coloured LED indicating operating status

Off

No power supply

Green blinking

Moving to position

Green blinking

End stroke confirmation

Green fixed

End stroke reached

Red blinking

Cycle

Red fixed

4/20 mA or 2/10 VDC signal lost

Settings 

RVAPC-24A features 6 DIP switches allowing to set the range, the ac-

tion type, the curve and the signal type.
By default all DIP switches are set to OFF (0...10 V DC, linear, direct 
action).
DIP switch 1-3: control signal range
DIP switch 4: Action
DIP switch 5: Curve
DIP switch 6: Signal type

RVAPC-24A

11518C

 

APR 18

EN

1

DIP switches

Jumper