Regin RVAN25-24A Instruction Download Page 1

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAN25-24A

1

Valve actuator for 0(2)...10 V control

RVAN25-24A is a valve actuator designed for control of Regin valves. 
The actuator has automatic self stroke adjustment and can be oper-
ated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

 

 

or 24 V DC ±15 % 

Control signal 

 

0(2)...10 V DC 

Max. power consumption  8.6 W / 22.4 VA 
Stroke 

 

10...52 mm 

Stroke time 

 

3 s/mm 

Force 

 

2500 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions (WxHxD) 

198 x 309 x 133 mm 

Protection class   

IP54

Installation

If the valve stem lock and valve throat adaptor are not already mounted 
on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the screws (hex key 6 mm) and clamp from the actuator yoke.

Depress the spring-loaded tab on the drive rod coupling device and fit the 

valve stem into the coupling.
Release the tab to connect the valve to the actuator. The position of the 
yoke on the valve stem adaptor must be adjusted so that the clamp screw 
holes line up with the groove in the valve throat adaptor. If the drive rod 
needs to be moved in or out for this, depress the central button of the 
control knob and turn it clockwise to extend the drive rod and counter-
clockwise to retract it (see Manual override). Mount the screws and the 

clamp. Tighten the screws until the actuator is firmly attached. 

Disassembly takes place in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and end position calibration

Stroke and end position calibration is not necessary due to a con-
struction utilizing end position stops. When the valve reaches the end 
position, a force is generated. Once the force of the actuator reaches 

a predefined level, the limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are six DIP switches for setting different functions. Follow the 

table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

RVAN25-24A

10579D

 

MA

Y 18

EN

Summary of Contents for RVAN25-24A

Page 1: ...irmly attached Disassembly takes place in reverse order Mounting positions 90 90 Wiring 24 V AC DC 1 2 3 4 5 1 2 3 4 5 6 Override input Y 0 2 10 V DC Control signal from controller U 0 10 V DC Measuri...

Page 2: ...ation or the valve stroke lost Red light quick flashing Manual override mode End position markers There is a red and a blue plastic end position marker on the actuator linkage The markers can easily b...

Page 3: ...irekt verkan FI SW5 Y signalsplit enligt inst llning av SW6 Ingen splitfunktion FI SW6 5 6 10 V 0 100 0 2 5 6 V 0 100 FI SW1 Ventilens arbetsriktning On Ventilen r st ngd n r spindeln r i sitt nedre l...

Page 4: ...riebsstange hierf r bewegt werden m ssen ist der mittlere Teil des Steuerknopfs zu dr cken und zu drehen im Uhrzeigersinn bewegt die Antriebs stange nach unten gegen den Uhrzeigersinn nach oben Schrau...

Page 5: ...t einem 4 20 mA Stellsignal angesteuert werden In diesem Falle ist ein 500 Widerstand zwischen Stellsignale ingang Kl 3 und Neutralleiter Kl 2 anzubringen und SW3 muss auf On 2 10 V DC stehen Dann wir...

Page 6: ...0 2 10 V DC U 0 10 V DC Signal neutre Signal de commande du r gulateur Tension de mesure pour l indicateur de position Entr e for age Y U B M G0 G talonnage de la course et des limites L talonnage de...

Page 7: ...Off 0 5 V 0 100 2 6 V quand SW3 On Indications Le moteur est quip de deux LEDs dont la signification est d crite dans le tableau ci dessous Indication Voyant vert fixe L actionneur fonctionne correcte...

Reviews: