Regin RVAN25-24 Instructions Download Page 1

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAN25-24

Valve actuator for 3-point control

RVAN25-24 is a valve actuator designed for control of Regin valves. 
For more info, see the product sheet of each valve. The actuator can 
also be combined with other brands of valves using adapter kits. The 
actuator can be operated manually.

Technical data

Supply voltage 

 

24 V AC ±15%, 50/60 Hz 

Control signal 

 

3-point 

Max. power consumption  10.9 W / 11.7 VA 
Stroke 

 

10...52 mm 

Stroke time 

 

3 s/mm 

Force 

 

2500 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90% RH 

Dimensions (WxHxD) 

200 x 300 x 135 mm 

Protection class   

IP54

Installation

If the valve stem lock and valve throat adaptor are not already mounted 
on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the screws (hex key 6 mm) and clamp from the actuator yoke. 

Depress the spring-loaded tab on the drive rod coupling device and fit the 

valve stem into the coupling.
Release the tab to connect the valve to the actuator. The position of the 
yoke on the valve stem adaptor must be adjusted so that the clamp screw 
holes line up with the groove in the valve throat adaptor. If the drive rod 
needs to be moved in or out for this, depress the central button of the 
control knob and turn it clockwise to extend the drive rod and counter-
clockwise to retract it (see Manual override). Mount the screws and the 

clamp. Tighten the screws until the actuator is firmly attached. 

Disassembly takes place in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC

1

2

3

1

2

3

G2 G1

G1 closed = Actuator spindle extending

G2 closed = Actuator spindle retracting

 

Calibration

Field calibration is not required. Once the valve reaches its end posi-
tion, a force builds up. When the force reaches the set level, a lever 
within the actuator operates a switch that stops the motor. 

 

Manual override

To manually set the valve position, first depress the central part of 
the button until it clicks and remains depressed (1 in the figure). This 

disengages the gears and also cuts the power to the motor. Then 
the valve position can be changed manually by turning the button (2 

in the figure). Clockwise rotation will extend the drive rod and anti-

clockwise will retract it. 

To reconnect power, set the button so the flats are in line with the 

cutout in the edge of the cover, Auto position. Then press on the outer 

parts of the button (3 in the figure). The central depressed part will 

pop out re-engaging the gears and reconnecting the power.

CE