RC-H is a room controller from the Regio Mini series, intended to 

control heating and cooling in a zone control system. Installation is 

directly on the wall or on an electrical connection box. The controller 
does not have a communication connection. 

Technical data

Supply voltage 

18...30 V AC, 50...60 Hz

Internal consumption 

2.5 VA

Ambient temperature 

0...50°C

Ambient humidity 

Max 90% RH

Storage temperature 

-20...+70°C

Built-in temperature sensor  NTC Type, range 0...50°C, accuracy  

+/-0.5°C at 15...30°C

Inputs and outputs 

Refer to connection illustrations and 

table below

Connection terminals 

Lift type for cable cross-section 2.1 mm

2

Protection class 

IP20

Material, casing 

Polycarbonate, PC

Weight 

110 g

Dimensions 

95 x 95 x 28 mm

Installation

Place the controller in a location that has a temperature representative for 

the room. A suitable location is approx. 1.6 m above floor level in a place 

with unobstructed air circulation.

Remove the frame by depressing the locking tab in the lower edge of the 

cover with a screwdriver. See figure 1.

Then prize out the electronics cassette using the four rectangular screwdri-

ver slots and levering against the edge of the bottom plate. See figure 2.

Note:

 Take care not to damage the electronics when inserting the screw-

driver into the slots. 

Figure 1

Figure 2

The bottom plate with terminals has a number of fixing hole combina

-

tions. Select suitable holes (see figure 3) and screw the bottom plate onto 

the wall or connection box, so that the arrows on the bottom plate point 
upwards. Do not tighten the screws too hard! 
With surface-mounted cabling, break-out suitable holes from the marks in 
the plastic.

Figure 3. Bottom plate with mounting alternatives and location of 

terminals (dimensions in mm.)

60

68

Figure 4. Connection diagram for RC-H

30
31
32
33

°C

°C

+

-

24 V AC

40
41
42
43

20
21
22
23
24

10
11
12
13
14

+C
AGnd
-
-

AI1
UI1
DI1
DI2/CI

G
G0
DO1
-
-

GDO
G0
-
UO1
UO2

G0

G

G

G0

Y

G

G0

Y

Figure 5. Alternative connection for terminals 31, UI1, and terminal 

33, DI2/CI, terminal 23, UO1, and terminal 24, UO2.

+

-

30
31
32
33

40
41
42
43

20
21
22
23
24

10
11
12
13
14

+C
AGnd
-
-

AI1
UI1
DI1
DI2/CI

G
G0
DO1
-
-

GDO
G0
-
UO1
UO2

Follow table 1 below for setting. (FS) in the text indicates factory set

-

ting.

Table 1. I/O connection terminals 

Ter-

minal

Desig-

nation

Operation

10

G

Supply voltage 24 V AC

11

G0

Supply voltage 0 V

12

DO1

For forced ventilation. 24 V AC output, max 0.5 A. 
24 V AC actuator is connected between terminal 
12 and terminal 20, GDO.

13-14

No function

EN

10 11 12 13 14

20 21 22 23 24

30 31 32 33

40 41 42 43

UP

UP

Summary of Contents for Regio Mini RC-H

Page 1: ...rewdri ver slots and levering against the edge of the bottom plate See figure 2 Note Take care not to damage the electronics when inserting the screw driver into the slots Figure 1 Figure 2 The bottom...

Page 2: ...ntact A potential free contact is connected between terminals 31 and 41 AGnd 32 DI1 Occupancy detector A potential free contact is connected between terminals 32 and 40 C Closed contact corresponds to...

Page 3: ...om a heating setpoint 22 C or a cooling setpoint 24 C that can be changed locally using i L s denna instruktion innan produkten monteras och ansluts INSTRUKTION REGIO RC H Rumsregulator RC H r en rums...

Page 4: ...change over F r 0 10 V DC ventilst lldon max 5 mA FI Ventilst lldonets 0 10 V styrsignalplint ansluts till plint 23 och dess matningsplintar till plint 10 och 11 Notera s att referenspol G0 ansluts p...

Page 5: ...ge over funktion kan aktiveras se nedan Change over funktion RC H har ing ng f r change over som automatiskt st ller om utg ng UO1 att verka med v rme eller kylfunktion Ing ngen kan anslutas till giva...

Page 6: ...Installation Monter le r gulateur dans un endroit repr sentatif de la temp rature dans la pi ce et qui ne pr sente pas d obstacle la libre circulation de l air La hauteur de montage est de 1 6 m au d...

Page 7: ...e de contr le du refroidissement Pour des moteurs de vannes 0 10 V DC max 5 mA RU La borne du signal de commande 0 10 V de l actionneur est branch e la borne 24 et les bornes d alimentation lectrique...

Page 8: ...re se fait sur le r gulateur Eco Stand by Le chauffage et le refroidissement sont arr t s dans un certain intervalle de temp rature autour de la consigne point de consigne chauffage 3 C point de consi...

Page 9: ...bb 2 Hinweis Bitte vorsichtig sein damit die Elektronik nicht vom Schrau bendreher besch digt wird Abb 1 Abb 2 Der Sockel mit Klemmen hat mehrere Befestigungsbohrungen W hlen Sie f r die Montage die g...

Page 10: ...hnitt Pr senz melder 33 DI2 CI Regin Kondensationsmelder KG A 1 WE Der F hler wird zwischen Klemmen 33 und 41 AGnd angeschlossen Alternativ Fensterkontakt DI Ein potentialfreier Kontakt wird zwischen...

Page 11: ...e Betriebsmodus Er kann mit dem DIP Schalter SW3 auf Standby geschaltet werden Siehe Tabelle 3 oben Pr senzmelder Um das Umschalten zwischen Standard Betriebsmodus und Bypass vor Ort zu steuern wird e...

Reviews: