Fan kick-start see section
.
✓
Fan afterblow see section
2.5.1
EC fan control
The EC fan control function is enabled and the EC fan control configuration settings are shown in
Application tool when the configuration value listed in
is configured on a controller output.
Figure 2-26 EC fan control configuration settings in Application tool.
The controller outputs a fan speed signal, Y1, that is configured on a controller output by using the value in
.
In auto mode, the Y1 signal corresponds to the current heating or cooling demand, as illustrated in
In manual mode, the Y1 signal is independent of the current heating or cooling demand. Instead, the fan
speed 1, 2, and 3 signals are defined by a number of equal thirds relative to the
Limit maximum EC fan speed
to (%)
configuration setting, as illustrated in
. For example, the fan speed 1 signal is equal to 0.33
times the set maximum fan speed value, and the fan speed 2 signal is equal to 0.67 times the set maximum
fan speed value.
Table 2-15 EC fan control configuration value and controller input type.
Output signal
Controller output configuration value
Controller output type
Y1
EC fan
Analog
The EC fan control configuration settings are described in
30
Regio
Eedo
manual, Rev. D