Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioCVDeadbandHeat2
194
2
1
DeadBand increase/decrease (%)
RCPSettings.RegioCVDeadbandCool1
195
2
1
DeadBand increase/decrease (%)
RCPSettings.RegioCVDeadbandCool2
196
2
1
Not used
RCPSettings.RegioCVDeadbandHeatCool
197
2
1
DeadBand increase/decrease (%)
RCPSettings.RegioCVDeadbandVAV
198
2
1
DeadBand increase/decrease (%)
RCPSettings.RegioCVDeadbandECFan
199
2
1
DeadBand increase/decrease (%)
RCPSettings.RegioPropValveHeat1PeriodTime
207
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveHeat2PeriodTime
208
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveCool1PeriodTime
209
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveCool2PeriodTime
210
210
1
Not used
RCPSettings.
RegioPropValveHeatCoolPeriodTime
211
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveVAVPeriodTime
212
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveECFanPeriodTime
213
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioCVHeatExerciseDay
221
8
1
Day for exercise heating and heat/cool valve:
0=Never
1-7=mon-sun
8=every day
RCPSettings.RegioCVCoolExerciseDay
222
8
1
Day for exercise cooling valve:
0=Never
1-7=mon-sun
8=every day
RCPSettings.RegioCVHeatExerciseHour
223
15
1
Hour for exercise heating and heat/cool valve
RCPSettings.RegioCVCoolExerciseHour
224
15
1
Hour for exercise cooling valve
RCPSettings.RegioCVHeatExerciseMin
225
0
1
Minute for exercise heating valve
RCPSettings.RegioCVCoolExerciseMin
226
0
1
Minute for exercise cooling valve
RCPSettings.RegioHeatExerciseTime
227
120
1
Time in seconds to Exercise the Heat Valves
RCPSettings.RegioCoolExerciseTime
228
120
1
Time in seconds to Exercise the Cool Valves
RCPSettings.
RegioSixWayValveFirstSeqFullyOpen
229
0
10
6 Way valve tension (V) for fully open on 1st
sequence
RCPSettings.
RegioSixWayValveFirstSeqStartOpen
230
3.3
10
6 Way valve tension (V) for start open on 1st
sequence
RCPSettings.
RegioSixWayValveSecondSeqStartOpen
231
6.7
10
6 Way valve tension (V) for start open on 2nd
sequence
RCPSettings.
RegioSixWayValveSecondSeqFullyOpen
232
10
10
6 Way valve tension (V) for fully open on 2nd
sequence
RCPSettings.RegioSixWayValveCenterPoint
233
5
10
6 Way valve tension (V) for center point
RCPSettings.RegioSixWayValveCenterPointHyst
234
2
1
6 Way valve centerpoint hysteresis (%)
RCPSettings.RegioAi1Comp
249
0
10
Analog input 1 compensation
RCPSettings.RegioAi2Comp
250
0
10
Analog input 2 compensation
RCPSettings.RegioAi3Comp
251
0
10
Analog input 3 compensation
RCPSettings.RegioAi4Comp
252
0
10
Analog input 4 compensation
RCPSettings.RegioCond_0V
253
0
1
Condense at 0 Volt input
RCPSettings.RegioCond_10V
254
100
1
Condense at 10 Volt input
RCPSettings.RegioCO2_0V
255
0
1
CO2 at 0 Volt input
RCPSettings.RegioCO2_10V
256
2000
1
CO2 at 10 Volt input
RCPSettings.RegioRH_0V
257
0
1
RH at 0 Volt input
RCPSettings.RegioRH_10V
258
100
1
RH at 10 Volt input
90
Regio
Eedo
manual, Rev. D