Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioDo1
159
7
1
Configuration for Digital Output 1
0 =Disabled
1 =Fan speed 1
2 =Fan speed 2
3 =Fan speed 3
4 =Lighting
5 =Blind in
6 =Blind out
7 =Forced ventilation
8 =Heat valve Inc.
9 =Heat valve Dec
10=Heat valve thermal(PWM)
11=Heat valve 2 Inc.
12=Heat valve 2 Dec.
13=Heat valve 2 thermal(PWM)
14=Cool valve Inc.
15=Cool valve Dec.
16=Cool valve thermal(PWM)
17=Not used
18=Not used
19=Not used
20=Change over valve Inc
21=Change over valve Dec
22=Change over thermal(PWM)
23=SumAlarm
24=SumAlarm A
25=SumAlarm B
117=Not used
118=Not used
119=Not used
RCPSettings.RegioDo2
160
23
1
Configuration for Digital Output 2
RCPSettings.RegioDo3
161
0
1
Configuration for Digital Output 3
RCPSettings.RegioDo4
162
0
1
Configuration for Digital Output 4
RCPSettings.RegioDo5
163
0
1
Configuration for Digital Output 5
RCPSettings.RegioDo6
164
0
1
Configuration for Digital Output 6
RCPSettings.RegioHeatValve1Type
165
0
1
Output Signal for HeatValve1:
0=0-10V
1=2-10V
2=10-2V
3=10-0V
4=Inc/Dec
5=PWM(Thermal)
6=6 Way-vay valve
RCPSettings.RegioHeatValve2Type
166
0
1
Output Signal for HeatValve2:
RCPSettings.RegioCoolValve1Type
167
0
1
Output Signal for CoolValve1:
RCPSettings.RegioCoolValve2Type
168
0
1
Output Signal for CoolValve2:
RCPSettings.RegioHeatCoolValveType
169
0
1
Output Signal for ChangeOver/6-WayValve
RCPSettings.RegioVAVType
170
0
1
Output Signal for VAV
RCPSettings.RegioECFANType
171
0
1
Output Signal for EC-Fan
RCPSettings.RegioValveHeat1RunTime
179
120
1
Run time (sec) closed to opened valve Heat 1
RCPSettings.RegioValveHeat2RunTime
180
120
1
Run time (sec) closed to opened valve Heat 2
RCPSettings.RegioValveCool1RunTime
181
120
1
Run time (sec) closed to opened valve Cool 1
RCPSettings.RegioValveCool2RunTime
182
120
1
Not used
RCPSettings.RegioValveHeatCoolRunTime
183
120
1
Run time (sec) closed to opened valve HeatCool
RCPSettings.RegioValveVAVRunTime
184
120
1
Run time (sec) closed to opened valve VAV
RCPSettings.RegioValveECFanRunTime
185
120
1
Run time (sec) closed to opened valve ECFan
RCPSettings.RegioCVDeadbandHeat1
193
2
1
DeadBand increase/decrease (%)