
Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioAi2
144
0
1
Configuration for Analog Input 2
RCPSettings.RegioAi3
145
0
1
Configuration for Analog Input 3
RCPSettings.RegioAi4
146
0
1
Configuration for Analog Input 4
RCPSettings.RegioDi1
147
3
1
Configuration for Digital Input 1
0=Disable
1=Open window
2=Not Used
3=Presence detector
4=Changeover
101=Open window room 2
102=Not used
103=Presence detector room 2
RCPSettings.RegioDi2
148
1
1
Configuration for Digital Input 2
RCPSettings.RegioDi3
149
0
1
Configuration for Digital Input 3
RCPSettings.RegioDi4
150
0
1
Configuration for Digital Input 4
RCPSettings.RegioCI
153
1
1
Configuration for Digital Condensation Input 1:
0=Disable
1=Regin's KG-A/1 sensor
2=Regin's KG-A/1 sensor room 2
RCPSettings.RegioCI2
154
0
1
Configuration for Digital Condensation Input 2
RCPSettings.RegioAo1
155
1
1
Configuration for Analog Output 1
0=Disable
1=Heat
2=Heat 2
3=Cool
4=Not used
5=Changeover / 6-Way Valve
6=VAV
7=EC-Fan
101=Heat room 2
102=Heat 2 room 2
103=Cool room 2
104=Not used
105=Changeover / 6-Way valve room 2
106=VAV room 2
107=Ec-Fan room 2
RCPSettings.RegioAo2
156
3
1
Configuration for Analog Output 2
RCPSettings.RegioAo3
157
6
1
Configuration for Analog Output 3
RCPSettings.RegioAo4
158
0
1
Configuration for Analog Output 4
88
Regio
Eedo
manual, Rev. D