Signal name
Modbus
address
Default
value
Description
RCPSettings.RegioUseRemoteValues
49
1
If 1 it will show in the RU the network avalues from the
master controller(All controllers Average) if 0 will display
i'ts own room temperature
RCPSettings.RegioRUConfigMenuDisableZone2
50
0
Enable entering the configuration menu in the RU unit
when pressing the UP and Down Key
RCPSettings.RegioUseRemoteValuesZone2
51
1
If 1 it will show in the RU the network avalues from the
master controller(All controllers Average) if 0 will display
i'ts own room temperature
RCPSettings.RegioForceDisplayID
52
0
Forces the Display to identify themselves(show number on
display/blink leds), can leave this state by pressing On/Off
button
RCPSettings.RegioDisplayIDOnPowerUp
53
0
If enabled will show display identification on power for 60
seconds or press of the on/off button
RCPSettings.RegioForceDisplaySearch
54
0
Trigger a search for display on display port
RCPSettings.RegioDisable2ndSequence
56
0
If enabled when Condensation input is active in modes with
2 sequences the 2nd sequence will also be set to 0%
RCPSettings.RegioDisable2ndSequenceZone2
57
0
If enabled when Condensation input is active in modes with
2 sequences the 2nd sequence will also be set to 0%
Room2
RCPSettings.RegioTcpIpMasterAddrCommit
58
1
-
RCPSettings.RegioModbusIpEnable
59
0
Enables ModBus IP
RCPSettings.RegioBACnetIpEnable
60
1
Enables BACnet IP datalink
RCPSettings.RegioLogActive
61
1
Activate log function for EXOScada
RCPSettings.RegioAutoSummerTime
62
1
Switch automatically between summer and winter time
RCPSettings.RegioRemovableWallsMaster
63
0
Set to 1 to enable master Multiple Controllers on Port
Define on RemovableWallsCommPort
RCPSettings.RegioRemovableWallsSlave
64
0
Set to 1 to enable slave Multiple Controllers on Port Define
on RemovableWallsCommPort
RCPSettings.RegioUseMasterValues
65
0
Set to 1 to enable Removable walls but only use the
master sensors values to feed into the control loop
RCPSettings.RegioRemoteRoomTempSelect
66
0
Room Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteAIChangeOverSelect
67
0
ChangeOver Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteOutDoorTempSelect
68
0
Outdoor Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteCondenseSelect
69
0
Condensation Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomCO2Select
70
0
CO2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomRHSelect
71
0
RH Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteSupplyAirSelect
72
0
Supply Air Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteDIOpenWindowSelect
79
0
Open Window Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)