Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
3
RCPSettings.RegioControllerStatePresence
4
Presence operating mode:
3=Occupied
4=ByPass
4
RCPSettings.RegioControllerStateRemote
5
Is used for remote control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No remote control
5
RCPSettings.RegioControllerStateBypassTime
120
min
Time for Bypass mode (Min)
6
RCPSettings.RegioChangeOverSelect
2
Select Change Over:
0=heating
1=cooling
2=Auto
7
RCPSettings.RegioChangeOverType
0
Type of Changeover used in Room 1 0-Digital
(Thermostat) 1-Analog Temperature in
IncomingPipe
8
RCPSettings.RegioChangeOverAIDiffHeat
3
°C
The difference between the temperature in the
room and the media temperature for change
over to cooling
9
RCPSettings.RegioChangeOverAIDiffCool
4
°C
The difference between the temperature in the
room and the media temperature for change
over to heating
10
RCPSettings.RegioCO2PresenceDetection
1
Activate presence on CO2
11
RCPSettings.RegioCO2PresenceLimit
800
Activate presence if CO2 is higher
12
RCPSettings.RegioLightControlFunction
0
Select light control function
0=Central controlled
1=Local Time controlled
2=Presence controlled
3=Time or Presence controlled
4=Central controlled or Presence controlled
21
RCPSettings.RegioAutoSummerTime
1
Switch automatically between summer and
winter time
22
Qsystem.Sec
-
sec
System Time Seconds
23
Qsystem.Minute
-
min
System Time Minutes
24
Qsystem.Hour
-
hour
System Time Hours
25
Qsystem.WDay
-
System WeekDay
26
Qsystem.Week
-
System Week
27
Qsystem.Date
-
System Date Day
28
Qsystem.Month
-
System Date Month
29
Qsystem.Year
-
System Date Year
B.3 ACTR
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioVAVOutputMinLimitOff
0
%
Min Limit for VAV Output at off State
2
RCPSettings.RegioVAVOutputMinLimitUno
10
%
Min Limit for VAV Output at Unoccupied State
3
RCPSettings.RegioVAVOutputMinLimitStandby
10
%
Min Limit for VAV Output at Stanby State
4
RCPSettings.RegioVAVOutputMinLimitOcc
20
%
Min Limit for VAV Output at Occupied or
Bypass State
5
RCPSettings.RegioVAVOutputMaxLimit
100
%
Max Limit for VAV Output