Table 3-7 Display configuration settings.
Configuration setting
Description
View mode
One of the following options is selected:
✓
Temperature:
The room temperature is shown (default setting).
✓
Heating setpoint:
The occupied heating setpoint, including setpoint adjustment, is
shown.
✓
Cooling setpoint:
The occupied cooling setpoint, including setpoint adjustment, is
shown.
✓
Average of cooling and heating setpoint:
The average of the occupied cooling
and heating setpoint, including setpoint adjustment, is shown.
✓
Setpoint adjustment:
The setpoint adjustment is shown.
✓
CO2 level:
The CO
2
level in the room is shown.
View mode during setpoint adjustment
One of the following options is selected:
✓
Setpoint adjustment:
The setpoint adjustment is shown (default setting).
✓
Controlling setpoint:
The occupied heating or cooling setpoint, including setpoint
adjustment, that is used for control is shown.
✓
Heating setpoint:
The occupied heating setpoint, including setpoint adjustment, is
shown.
✓
Cooling setpoint:
The occupied cooling setpoint, including setpoint adjustment, is
shown.
Alternate between view mode setting and
CO2 level
Enabled:
The display alternates between showing the current
View mode
setting and
the CO
2
level in the room (default setting).
Disabled:
The current
View mode
setting is shown.
Brightness when lit (%)
Specifies the display background brightness when lit.
Brightness when dimmed (%)
Specifies the display background brightness when dimmed. The brightness is dimmed
after 2 minutes of inactivity.
Parameter menu access
Enabled:
The parameter menu is accessible (default setting).
Disabled:
The parameter menu is not accessible.
3.7.4
Buttons/switch and knob
This section describes the buttons/switch and knob configuration settings.
Table 3-8 Buttons/switch and knob configuration settings.
Configuration setting
Description
Enabled buttons/switch and knob
One of the following options is selected:
✓
All disabled
✓
Occupancy button
✓
Fan button/switch
✓
Up/down buttons, knob
✓
Occupancy button, up/down buttons, knob
✓
Fan button/switch, up/down buttons, knob
✓
All enabled
(default setting)
Note:
The parameter menu in room units with display is accessible even if the up/down
buttons are not enabled.
Occupancy button press time for shutdown
controller state (s)
The period of time (in seconds) that the occupancy button must be pressed (long
press) for the controller to change to the state specified by the
Shutdown controller
state
setting.
56
Regio
Eedo
manual, Rev. D