illustrates the control behaviour when no maximum or minimum limits are set for the output
signals.
Figure 2-21 Control behaviour for the standby controller state.
Occupied and Bypass
In these states, the controller regulates based on the configured occupied heating and cooling setpoints.
Setpoint adjustment is active in these controller states.
The forced ventilation function can be used when the controller changes to bypass state. See section
for
information about the forced ventilation function.
Active setpoints:
The configured occupied heating and cooling setpoints, combined with any applied
setpoint adjustment.
illustrates the control behaviour when no maximum or minimum limits are set for the output
signals.
Figure 2-22 Control behaviour for the occupied and bypass controller state.
2.4.2
Configuration settings
The controller state configuration settings are described in
Heating signal
Cooling or VAV signal
Heating signal
Cooling or VAV signal
Output
Max: 100%
Occupied
heating
setpoint
Occupied
cooling
setpoint
Min: 0%
100%
100%
0%
0%
Cooling demand
Heating demand
Room temperature
Setpoint
adjustment
Setpoint
adjustment
Regio
Eedo
manual, Rev. D
25