Signal name
Object name
Instance
number
Writeable Description
RCPActual.
RegioDIPresenceCombined
RegioDIPresenceCom-
bined
20097
NO
Pressens indication all Controllers (This is
the combination of all pins not actualy the
presence state)
RCPActual.
RegioDIChangeoverCombined
RegioDIChangeoverCom-
bined
20098
NO
Change over indication all Controllers
D.3 Analog values
Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioHeatSetPointOccupied
RegioHeatSetPointOccu-
pied
30001
YES
Room Base setpoint heating
RCPSettings.
RegioCoolSetPointOccupied
RegioCoolSetPointOccu-
pied
30002
YES
Room Base setpoint cooling
RCPSettings.
RegioRoomTempPBand
RegioRoomTempPBand
30003
YES
Temperature PID P Band
RCPSettings.
RegioRoomTempITime
RegioRoomTempITime
30004
YES
Temperature PID I Time
RCPSettings.
RegioHeatSetPointUnoccupied
RegioHeatSetPointUnoc-
cupied
30005
YES
Setpoint heating in Unoccupied
RCPSettings.
RegioCoolSetPointUnoccupied
RegioCoolSetPointUnoc-
cupied
30006
YES
Setpoint Cooling in Unoccupied
RCPSettings.
RegioSetPointDeadBandStandby
RegioSetPointDeadBand-
Standby
30007
YES
Deadband in Standby mode
RCPSettings.
RegioFrostProtectionSetPoint
RegioFrostProtectionSet-
Point
30008
YES
Setpoint frostprotection
RCPSettings.
RegioSetPOffsetRemote
RegioSetPOffsetRemote
30009
YES
Setpoint Offset Remote
RCPSettings.
RegioControllerStateBypassTime
RegioControllerStateBy-
passTime
30011
YES
Time for Bypass mode (Min)
RCPSettings.
RegioVAVOutputMinLimitOff
RegioVAVOutputMinLi-
mitOff
30012
YES
Min Limit for VAV Output at off State
RCPSettings.
RegioVAVOutputMinLimitUno
RegioVAVOutputMinLimi-
tUno
30013
YES
Min Limit for VAV Output at Unoccupied
State
RCPSettings.
RegioVAVOutputMinLimitStandby
RegioVAVOutputMinLimit-
Standby
30014
YES
Min Limit for VAV Output at Stanby State
RCPSettings.
RegioVAVOutputMinLimitOcc
RegioVAVOutputMinLimi-
tOcc
30015
YES
Min Limit for VAV Output at Occupied or
Bypass State
RCPSettings.
RegioVAVOutputMaxLimit
RegioVAVOutputMaxLimit
30016
YES
Max Limit for VAV Output
RCPSettings.
RegioChangeOverAIDiffHeat
RegioChangeOverAIDiff-
Heat
30018
YES
The difference between the temperature in
the room and the media temperature for
change over to cooling
RCPSettings.
RegioChangeOverAIDiffCool
RegioChangeOverAIDiff-
Cool
30019
YES
The difference between the temperature in
the room and the media temperature for
change over to heating
RCPSettings.RegioSupplyAirTem-
pLimCascadeFactor
RegioSupplyAirTempLim-
CascadeFactor
30020
YES
Cascade Factor for the Cascade PID
RCPSettings.RegioSupplyAirTem-
pLimHeatMinLimit
RegioSupplyAirTempLim-
HeatMinLimit
30021
YES
Min Setpoint for the Cascade PID in Heat
Mode
RCPSettings.RegioSupplyAirTem-
pLimHeatMaxLimit
RegioSupplyAirTempLim-
HeatMaxLimit
30022
YES
Max Setpoint for the Cascade PID in Heat
Mode
Regio
Eedo
manual, Rev. D