Signal name
Modbus
address
Default
value
Description
RCPSettings.RegioRemoteDIPresenceSelect
80
0
Presence Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteDIChangeoverSelect
81
0
ChangeOver State Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteDICondenseAlarmSelect
82
0
Condensation State Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteDIOpenWindowZone2Select
83
0
Open Window Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteDIPresenceZone2Select
84
0
Presence Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteDICondenseAlarmZone2Select
85
0
Condensation Room2 State Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteDIOpenWindow
86
0
Communication Open Window State
RCPSettings.RegioRemoteDIPresence
87
0
Communication Presence State
RCPSettings.RegioRemoteDIChangeover
88
0
Communication ChangeOver State
RCPSettings.RegioRemoteDICondenseAlarm
89
0
Communication Condensation State
RCPSettings.RegioRemoteDIOpenWindowZone2
90
0
Communication Open Window Room2 State
RCPSettings.RegioRemoteDIPresenceZone2
91
0
Communication Presence Room2 State
RCPSettings.
RegioRemoteDICondenseAlarmZone2
92
0
Communication Condensation Room2 State
C.2 Input registers
Signal name
Modbus
address
Scale
Description
RCPActual.RegioSoftware
1
1
Type of Regio software (0=RPC)
RCPActual.RegioVerMajor
2
1
Major Version
RCPActual.RegioVerMinor
3
1
Minor Version
RCPActual.RegioVerBranch
4
1
Branch Version (0=Beta, 1=Official)
RCPActual.RegioRevision
5
1
Revision
RCPActual.RegioRoomTempExt
6
10
Room temp external sensor
RCPActual.RegioAIChangeOverTemp
7
10
Change over
RCPActual.RegioOutdoorTemp
8
10
Outdoor temp
RCPActual.RegioCondensation
9
1
Condense
RCPActual.RegioRoomCO2
10
1
Room CO2
RCPActual.RegioRoomRH
11
1
Room RH
RCPActual.RegioSupplyAirTemp
12
10
SupplyAir Temperature
RCPActual.RegioAnaOut1
13
1
Analog output 1
RCPActual.RegioAnaOut2
14
1
Analog output 2
RCPActual.RegioAnaOut3
15
1
Analog output 1
RCPActual.RegioAnaOut4
16
1
Analog output 2
RCPActual.RegioHeatSeq1
17
1
Control valve Heating 1
Regio
Ardo
manual, Rev. D
95