Room unit display parameter lists
B.8 ALAM
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioAlarmHyst
0.2
Alarm hysteresis
2
RCPSettings.RegioRoomTempHighLimit
40
High room temp
3
RCPSettings.RegioRoomTempLowLimit
15
Low room temp
4
RCPSettings.RegioRoomTempMaxDeviationLimit
20
Max allowed difference between setpoint and
room temp before alarm
5
RCPSettings.RegioAlarmHystZone2
0.2
Alarm hysteresis Room2
6
RCPSettings.RegioRoomTempHighLimitZone2
40
High room temp Room2
7
RCPSettings.RegioRoomTempLowLimitZone2
15
Low room temp Room2
8
RCPSettings.
RegioRoomTempMaxDeviationLimitZone2
20
Max allowed difference between setpoint and
room temp before alarm Room2
9
RCPSettings.RegioCondenseLimit
80
High limit for condense alarm
10
RCPSettings.RegioCondenseHyst
2
Condense alarm hysteresis
11
RCPSettings.RegioCondenseLimitZone2
80
High limit for condense alarm Room2
12
RCPSettings.RegioCondenseHystZone2
2
Condense alarm hysteresis Room2
13
RCPSettings.RegioCO2MaxLimit
1500
ppm
Max CO2 Level for Alarm
14
RCPSettings.RegioCO2MaxLimitZone2
1500
ppm
Max CO2 Level for Alarm Room2
15
AlaData.AlaPt1_DelayValue
0
Delay value for point no. 1 Condensation
16
AlaData.AlaPt2_DelayValue
0
Delay value for point no. 2
CondensationZone2
17
AlaData.AlaPt3_DelayValue
0
Delay value for point no. 3 SensorAlarm
18
AlaData.AlaPt4_DelayValue
0
Delay value for point no. 4 SensorAlarmZone2
19
AlaData.AlaPt5_DelayValue
0
Delay value for point no. 5 Presence
20
AlaData.AlaPt6_DelayValue
0
Delay value for point no. 6 OpenWindow
21
AlaData.AlaPt7_DelayValue
0
Delay value for point no. 7 PresenceZone2
22
AlaData.AlaPt8_DelayValue
0
Delay value for point no. 8
OpenWindowsZone2
23
AlaData.AlaPt9_DelayValue
0
Delay value for point no. 9 RoomUnitError
24
AlaData.AlaPt10_DelayValue
0
Delay value for point no. 10
RoomUnitErrorZone2
25
AlaData.AlaPt11_DelayValue
0
Delay value for point no. 11 Slave1CommFail
26
AlaData.AlaPt12_DelayValue
0
Delay value for point no. 12 Slave2CommFail
27
AlaData.AlaPt13_DelayValue
0
Delay value for point no. 13 Slave3CommFail
28
AlaData.AlaPt14_DelayValue
0
Delay value for point no. 14 Slave4CommFail
29
AlaData.AlaPt15_DelayValue
0
Delay value for point no. 15 RoomTempHigh
30
AlaData.AlaPt16_DelayValue
0
Delay value for point no. 16 RoomTempLow
31
AlaData.AlaPt17_DelayValue
0
Delay value for point no. 17
RoomTempDeviation
32
AlaData.AlaPt18_DelayValue
0
Delay value for point no. 18
RoomControllerInManualMode
33
AlaData.AlaPt19_DelayValue
0
Delay value for point no. 19
RoomTempHighZone2
34
AlaData.AlaPt20_DelayValue
0
Delay value for point no. 20
RoomTempLowZone2
35
AlaData.AlaPt21_DelayValue
0
Delay value for point no. 21
RoomTempDeviationZone2
36
AlaData.AlaPt22_DelayValue
0
Delay value for point no. 22
RoomControllerInManualModeZone2
90
Regio
Ardo
manual, Rev. D