Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
31
RCPSettings.RegioCVHeatExerciseDayZone2
8
Day for exercise heating valve Room2:
0=Never
1-7=mon-sun
8=every day
32
RCPSettings.RegioCVCoolExerciseDayZone2
8
Day for exercise cooling valve Room2:
0=Never
1-7=mon-sun
8=every day
33
RCPSettings.RegioCVHeatExerciseHourZone2
15
hour
Hour for exercise heating valve Room2
34
RCPSettings.RegioCVCoolExerciseHourZone2
15
hour
Hour for exercise cooling valve Room2
35
RCPSettings.RegioHeatExerciseTimeZone2
120
sec
Time in seconds to Exercise the Heat Valves
for Room2
36
RCPSettings.RegioCoolExerciseTimeZone2
120
sec
Time in seconds to Exercise the Cool Valves
for Room2
B.4 FAN
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioFanControlMode
0
FanControl Mode
0=No control
1=Controlled by Heating
2=Controlled by cooling
3=Controlled by both heat and cooling
2
RCPSettings.RegioFanSpeed1Start
20
%
If higher controller output start fanspeed 1
3
RCPSettings.RegioFanSpeed2Start
60
%
If higher controller output start fanspeed 2
4
RCPSettings.RegioFanSpeed3Start
100
%
If higher controller output start fanspeed 3
5
RCPSettings.RegioFanSpeedHyst
5
%
Hysteresis % for start/stop fan
6
RCPSettings.RegioRUNoOfFanSpeeds
3
Configured number of fanspeeds (1-3)
7
RCPSettings.RegioMinFanSpeed
0
Min Speed for the fan:
0=Stop
1=Speed 1
8
RCPSettings.RegioFanStopTime
120
sec
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
9
RCPSettings.RegioFanAfterBlowMinSpeed
0
Minimum Fan Speed when FanafterBlow
Active
10
RCPSettings.RegioFanControlModeZone2
0
FanControl Mode Room2:
0=No control
1=Controlled by Heating
2=Controlled by cooling
3=Controlled by both heat and cooling
11
RCPSettings.RegioFanSpeed1StartZone2
20
%
If higher controller output start fanspeed 1
Room2
12
RCPSettings.RegioFanSpeed2StartZone2
60
%
If higher controller output start fanspeed 2
Room2
13
RCPSettings.RegioFanSpeed3StartZone2
100
%
If higher controller output start fanspeed 3
Room2
14
RCPSettings.RegioFanSpeedHystZone2
5
%
Hysteresis % for start/stop fan Room2
15
RCPSettings.RegioRUNoOfFanSpeedsZone2
3
Configured number of fanspeeds (1-3) Room2
16
RCPSettings.RegioMinFanSpeedZone2
0
Min Speed for the fan Room2:
0-=Stop
1=Speed 1
Regio
Ardo
manual, Rev. D
83