Room unit display parameter lists
B.3 ACTR
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioVAVOutputMinLimitOff
0
%
Min Limit for VAV Output at off State
2
RCPSettings.RegioVAVOutputMinLimitUno
10
%
Min Limit for VAV Output at Unoccupied State
3
RCPSettings.RegioVAVOutputMinLimitStandby
10
%
Min Limit for VAV Output at Stanby State
4
RCPSettings.RegioVAVOutputMinLimitOcc
20
%
Min Limit for VAV Output at Occupied or
Bypass State
5
RCPSettings.RegioVAVOutputMaxLimit
100
%
Max Limit for VAV Output
6
RCPSettings.RegioVAVOutputMinLimitOffZone2
0
%
Min Limit for VAV Output at off State Room2
7
RCPSettings.RegioVAVOutputMinLimitUnoZone2
10
%
Min Limit for VAV Output at Unoccupied State
Room2
8
RCPSettings.
RegioVAVOutputMinLimitStandbyZone2
10
%
Min Limit for VAV Output at Stanby State
Room2
9
RCPSettings.RegioVAVOutputMinLimitOccZone2
20
%
Min Limit for VAV Output at Occupied or
Bypass State Room2
10
RCPSettings.RegioVAVOutputMaxLimitZone2
100
%
Max Limit for VAV Output Room2
11
RCPSettings.RegioHeatValve1Type
0
Output Signal for HeatValve1:
0=0-10V
1=2-10V
2=10-2V
3=10-0V
4=Inc/Dec
5=PWM(Thermal)
6=6 Way-vay valve
12
RCPSettings.RegioHeatValve2Type
0
Output Signal for HeatValve2:
13
RCPSettings.RegioCoolValve1Type
0
Output Signal for CoolValve1:
14
RCPSettings.RegioCoolValve2Type
0
Output Signal for CoolValve2:
15
RCPSettings.RegioHeatCoolValveType
0
Output Signal for ChangeOver/6-WayValve
16
RCPSettings.RegioVAVType
0
Output Signal for VAV
17
RCPSettings.RegioECFANType
0
Output Signal for EC-Fan
18
RCPSettings.RegioHeatValve1TypeZone2
0
Output Signal for HeatValve Room2
19
RCPSettings.RegioHeatValve2TypeZone2
0
Output Signal for HeatValve2 Room2
20
RCPSettings.RegioCoolValve1TypeZone2
0
Output Signal for CoolValve1 Room2
21
RCPSettings.RegioCoolValve2TypeZone2
0
Output Signal for CoolValve2 Room2
22
RCPSettings.RegioHeatCoolValveTypeZone2
0
Output Signal for ChangeOver/6-WayValve
Room2
23
RCPSettings.RegioVAVTypeZone2
0
Output Signal for VAV Room2
24
RCPSettings.RegioECFANTypeZone2
0
Output Signal for EC-Fan Room2
25
RCPSettings.RegioCVHeatExerciseDay
8
Day for exercise heating and heat/cool valve:
0=Never
1-7=mon-sun
8=every day
26
RCPSettings.RegioCVCoolExerciseDay
8
Day for exercise cooling valve:
0=Never
1-7=mon-sun
8=every day
27
RCPSettings.RegioCVHeatExerciseHour
15
hour
Hour for exercise heating and heat/cool valve
28
RCPSettings.RegioCVCoolExerciseHour
15
hour
Hour for exercise cooling valve
29
RCPSettings.RegioHeatExerciseTime
120
sec
Time in seconds to Exercise the Heat Valves
30
RCPSettings.RegioCoolExerciseTime
120
sec
Time in seconds to Exercise the Cool Valves
82
Regio
Ardo
manual, Rev. D