Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
25
RCPSettings.RegioCoolSetPointUnoccupiedZone2
30
°C
Setpoint Cooling in Unoccupied Room2
26
RCPSettings.
RegioSetPointDeadBandStandbyZone2
3
°C
Deadband in Standby mode Room2
27
RCPSettings.RegioFrostProtectionSetPointZone2
8
°C
Setpoint frostprotection Room2
28
RCPSettings.
RegioSupplyAirTempLimCascadeFactorZone2
3
Cascade Factor for the Cascade PID Room2
29
RCPSettings.
RegioSupplyAirTempLimHeatMinLimitZone2
24
°C
Min Setpoint for the Cascade PID in Heat
Mode Room2
30
RCPSettings.
RegioSupplyAirTempLimHeatMaxLimitZone2
35
°C
Max Setpoint for the Cascade PID in Heat
Mode Room2
31
RCPSettings.
RegioSupplyAirTempLimCoolMinLimitZone2
12
°C
Min Setpoint for the Cascade PID in Cool
Mode Room2
32
RCPSettings.
RegioSupplyAirTempLimCoolMaxLimitZone2
24
°C
Max Setpoint for the Cascade PID in Cool
Mode Room2
33
RCPSettings.
RegioSupplyAirTempLimFrostProtSetPointZone2
8
°C
Supply Air Temp Frost Protection Temperature
Room2
34
RCPSettings.RegioCO2PBandZone2
100
CO2 PID P Gain Room2
35
RCPSettings.RegioCO2ITimeZone2
100
sec
CO2 PID I Time Room2
36
RCPSettings.RegioCO2SetpointZone2
600
ppm
Setpoint for CO2 PI Controller in PPM Room2
B.2 SYS
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioControllerStateReturn
3
Select return unit state:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
2
RCPSettings.RegioControllerStateShutDown
1
Select shutdown state :
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
3
RCPSettings.RegioControllerStatePresence
4
Presence operating mode:
3=Occupied
4=ByPass
4
RCPSettings.RegioControllerStateRemote
5
Is used for remote control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No remote control
5
RCPSettings.RegioControllerStateBypassTime
120
min
Time for Bypass mode (Min)
6
RCPSettings.RegioChangeOverSelect
2
Select Change Over:
0=heating
1=cooling
2=Auto
7
RCPSettings.RegioChangeOverType
0
Type of Changeover used in Room 1 0-Digital
(Thermostat) 1-Analog Temperature in
IncomingPipe
8
RCPSettings.RegioChangeOverAIDiffHeat
3
°C
The difference between the temperature in the
room and the media temperature for change
over to cooling
80
Regio
Ardo
manual, Rev. D