
Table 2-26 Configuration settings for the two rooms function.
Configuration setting
Description
Enable room 2
Disabled:
Two-room control is disabled (default setting).
Enabled:
Two-room control is enabled. When the two rooms
function is enabled, all configuration settings for room 2 are
displayed in all panes in Application tool.
2.10 CO
2
control
CO
2
control is a function that enables the controller to regulate based on fresh air demand. CO
2
control is
performed by connecting a CO
2
sensor, and by letting the controller control the VAV output signal based on
the CO
2
setpoint and the current CO
2
level in the room.
CO
2
control can be used together with the controller modes that include a VAV sequence:
✓
H VAV
✓
C VAV
✓
VAV
✓
H C VAV
CO
2
control is managed via the VAV control function, by applying the
VAV control
configuration setting,
see section
The CO
2
sensor is connected to and configured on an analog controller input by using the value listed in
. Regin's ED-RU-DOCS room unit has a built-in CO
2
sensor. When an ED-RU-DOCS room unit
is connected, the controller recognizes the built-in CO
2
sensor automatically, and no controller input
configuration is needed.
Table 2-27 CO
2
control configuration value and controller input type.
Configuration value
Controller input type
CO2 sensor
Analog
CO
2
control provides a specific setting, listed in
, that is only applicable for the controller modes
that include a cooling sequence. This setting is located in the
Configuration -> Control functions -> Controller
mode
pane in Application tool, and is shown when an applicable controller mode is selected.
Table 2-28 CO
2
control configuration setting.
Configuration setting
Description
Cooling sequence controlled by
Cooling demand:
The cooling output signal is controlled based
on the cooling setpoint and the current room temperature (default
setting).
VAV control selection:
The cooling output signal is controlled
according to the
VAV control
setting, see section
. That is,
either by:
✓
Cooling demand
✓
CO2 demand
✓
Cooling or CO2, the highest demand
illustrates the control behaviour for CO
2
control when a minimum limits is set for the VAV
output signal.
The demand for fresh air increases as the CO
2
level in the room rises. When the CO
2
level rises above the
CO
2
setpoint,
VAV signal
increases to respond to the fresh air demand. At 100% fresh air demand,
VAV
signal
reaches its maximum.
Regio
Ardo
manual, Rev. D
47