
Appendix D
BACnet signal lists
D.1 Multistate values
Signal name
Object name
Instance
number
Writeable Description
RCPSettings.RegioControllerMode
RegioControllerMode
40001
NO
Control Mode
1=Heating
2=H Heating
3=H Cooling
4=Cooling
5=Heating/Cooling (change-over)
6=H Heating/Cooling (change-over)
7=H VAV
8=C VAV
9=VAV
10=H C VAV
RCPSettings.
RegioControllerStateRemote
RegioControllerStateRe-
mote
30010
YES
Is used for remote control
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
6=No remote control
RCPSettings.
RegioChangeOverSelect
RegioChangeOverSelect
30017
YES
Select Change Over
1=Heating
2=Cooling
3=Auto
RCPSettings.
RegioFanAfterBlowMinSpeed
RegioFanAfterBlowMin-
Speed
30030
YES
Minimum Fan Speed when FanafterBlow
Active
1=Off
2=Speed1
3=Speed2
4=Speed3
RCPSettings.
RegioLightControlFunction
RegioLightControlFunction 30031
YES
Select light control function
1=Central controlled
2=Local Time controlled
3=Presence controlled
4=Time or Presence controlled
5=Central controlled or Presence controlled
RCPSettings.
RegioSunBlindsControl
RegioSunBlindsControl
30032
YES
Remote Control for the Jalusi
1=Go In
2=Stop
3=Go out
RCPSettings.
RegioControllerModeZone2
RegioControllerMode-
Zone2
40002
NO
Control Mode (Room2)
1=Heating
2=H Heating
3=H Cooling
4=Cooling
5=Heating/Cooling (change-over)
6=H Heating/Cooling (change-over)
7=H VAV
8=C VAV
9=VAV
10=H C VAV
RCPSettings.
RegioControllerStateRemoteZone2
RegioControllerStateRe-
moteZone2
30042
YES
Is used for remote control Zone2
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
6=No remote control
RCPSettings.
RegioFanAfterBlowMinSpeedZone2
RegioFanAfterBlowMinS-
peedZone2
30059
YES
Minimum Fan Speed when FanafterBlow
Active Room2:
1=Off
2=Speed1
3=Speed2
4=Speed3
118
Regio
Ardo
manual, Rev. D