Signal name
Modbus
address
Default
value
Description
RCPSettings.RegioDisable2ndSequenceZone2
57
0
If enabled when Condensation input is active in modes with
2 sequences the 2nd sequence will also be set to 0%
Room2
RCPSettings.RegioTcpIpMasterAddrCommit
58
1
-
RCPSettings.RegioModbusIpEnable
59
0
Enables ModBus IP
RCPSettings.RegioBACnetIpEnable
60
1
Enables BACnet IP datalink
RCPSettings.RegioLogActive
61
1
Activate log function for EXOScada
RCPSettings.RegioAutoSummerTime
62
1
Switch automaticly between summer and winter time
RCPSettings.RegioRemovableWallsMaster
63
0
Set to 1 to enable master Multiple Controllers on Port
Define on RemovableWallsCommPort
RCPSettings.RegioRemovableWallsSlave
64
0
Set to 1 to enable slave Multiple Controllers on Port Define
on RemovableWallsCommPort
RCPSettings.RegioUseMasterValues
65
0
Set to 1 to enable Removable walls but only use the
master sensors values to feed into the control loop
RCPSettings.RegioRemoteRoomTempSelect
66
0
Room Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteAIChangeOverSelect
67
0
ChangeOver Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteOutDoorTempSelect
68
0
Outdoor Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteCondenseSelect
69
0
Condensation Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomCO2Select
70
0
CO2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomRHSelect
71
0
RH Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteSupplyAirSelect
72
0
Supply Air Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteRoomTempZone2Select
73
0
Room Temperature Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteOutDoorTempZone2Select
74
0
Outdoor Temperature Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteCondenseZone2Select
75
0
Condensation Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomCO2Zone2Select 76
0
CO2 Room2 Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteRoomRHZone2Select
77
0
RH Room2 Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.
RegioRemoteSupplyAirTempZone2Select
78
0
Supply Air Room2 Temperature Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)
RCPSettings.RegioRemoteDIOpenWindowSelect
79
0
Open Window Source Selector:
0=Use Controller Input Values
1=use remote values (Exoline/Modbus/Bacnet)