7
RCPSettings.RegioRUDisplayViewType
0
Select view mode for the display:
0=Display value
1=Display Value with setpoint adjustment
2=Heat setpoint
3=Cool setpoint
4=Average cool/heat setpoint
5=Only setpoint offset
6=CO2 Level
8
RCPSettings.RegioRUDisplaySetPointType
0
Select view mode for the display when
pressing increase decrease button:
0=Setpoint offset
1=Controlling setpoint
2=Heat setpoint
3=Cool setpoint
9
RCPSettings.RegioRUButtonsUsed
7
Buttons that can be used in the RU
10
RCPSettings.RegioRUConfigMenuDisable
0
Enable entering the configuration menu in the
RU unit when pressing the UP and Down Key
11
RCPSettings.RegioRUDisplayBacklightLow
20
Lightning Lo (0-255)
12
RCPSettings.RegioRUDisplayBacklightHigh
100
Lightning Hi (0-255)
13
RCPSettings.RegioRUDisplayContrast
15
Contrast (0-15)
14
RCPSettings.RegioRUTypeZone2
9
Room Unit attached to the controller Room2:
0=None
1=ED-RU
2=ED-RU-O
3=ED-RU-F
4=ED-RU-FO
5=ED-RU-DO
6=ED-RU-DFO
7=ED-RU-DOS
8=ED-RU-H
9=ED-RU-DOCS
10=ED-RUD
15
RCPSettings.RegioRUTemperatureCompZone2
0
°C
Temperature Compensation for RU 2
16
RCPSettings.RegioRUDisplayViewTypeZone2
0
Select view mode for the display Room2:
0=Display value
1=Display Value with setpoint adjustment
2=Heat setpoint
3=Cool setpoint
4=Average cool/heat setpoint
5=Only setpoint offset
6=CO2 Level
17
RCPSettings.RegioRUDisplaySetPointTypeZone2
0
Select view mode for the display when
pressing increase decrease button Room2:
0=Setpoint offset
1=Controlling setpoint
2=Heat setpoint
3=Cool setpoint
18
RCPSettings.RegioRUButtonsUsedZone2
7
Buttons that can be used in the RU
19
RCPSettings.RegioRUConfigMenuDisableZone2
-
Enable entering the configuration menu in the
RU unit when pressing the UP and Down Key
20
RCPSettings.RegioRUDisplayBacklightLowZone2
20
Lightning Lo (0-255)
21
RCPSettings.RegioRUDisplayBacklightHighZone2
100
Lightning Hi (0-255)
22
RCPSettings.RegioRUDisplayContrastZone2
15
Contrast (0-15)
23
RCPSettings.RegioForceDisplayID
-
Forces the Display to identify themselves
(show number on display/blink leds), can leave
this state by pressing On/Off button
24
RCPSettings.RegioDisplayIDOnPowerUp
-
If enabled will show display identification on
power for 60 seconds or press of the on/off
button