Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
29
RCPSettings.RegioLightSelect
2
Manual/Auto of Lighting:
0=Off
1=On
2=Auto
30
RCPSettings.RegioSunBlindsInSelect
2
Manual/Auto of BlindIn
31
RCPSettings.RegioSunBlindsOutSelect
2
Manual/Auto of BlindOut
32
RCPSettings.RegioForcedVentSelect
2
Manual/Auto of ForceVentilation
33
RCPSettings.RegioDigOutSelectSumAlarm
2
Manual/Auto of SumAlarm
34
RCPSettings.RegioDigOutSelectSumAlarmA
2
Manual/Auto of SumAlarmA
35
RCPSettings.RegioDigOutSelectSumAlarmB
2
Manual/Auto of SumAlarmB
36
RCPSettings.RegioLightSelectZone2
2
Manual/Auto of Lighting Room2
37
RCPSettings.RegioSunBlindsInSelectZone2
2
Manual/Auto of BlindIn Room2
38
RCPSettings.RegioSunBlindsOutSelectZone2
2
Manual/Auto of BlindOut Room2
39
RCPSettings.RegioForcedVentSelectZone2
2
Manual/Auto of ForceVentilation Room2
40
RCPSettings.RegioDigOutSelectSumAlarmZone2
2
Manual/Auto of SumAlarm Room2
41
RCPSettings.RegioDigOutSelectSumAlarmAZone2
2
Manual/Auto of SumAlarmA Room2
42
RCPSettings.RegioDigOutSelectSumAlarmBZone2
2
Manual/Auto of SumAlarmB Room2
43
RCPSettings.RegioFanSelect
4
Fan speed Selected Remote/RegioTool:
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
44
RCPSettings.RegioFanSelectZone2
4
Fan speed Selected Remote/RegioTool
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
B.6 HMI
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioRUSetPointAdjPos
3
°C
Max allowed offset over setpoint
2
RCPSettings.RegioRUSetPointAdjNeg
3
°C
Max allowed offset below setpoint
3
RCPSettings.RegioRUSetPointAdjPosZone2
3
°C
Max allowed offset over setpoint Room2
4
RCPSettings.RegioRUSetPointAdjNegZone2
3
°C
Max allowed offset below setpoint Room2
5
RCPSettings.RegioRUType
9
Room Unit attached to the controller:
0=None
1=ED-RU
2=ED-RU-O
3=ED-RU-F
4=ED-RU-FO
5=ED-RU-DO
6=ED-RU-DFO
7=ED-RU-DOS
8=ED-RU-H
9=ED-RU-DOCS
10=ED-RUD
6
RCPSettings.RegioRUTempUnit
1
Display Unit:
0=None
1=°C
2=°F
Regio
Ardo
manual, Rev. D
85