Room unit display parameter lists
Appendix B
Room unit display parameter lists
B.1 CTRL
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioControllerMode
9
Control Mode
0=Heating
1=H Heating
2=H Cooling
3=Cooling
4=Heating/Cooling (change-over)
5=H Heating/Cooling (change-over)
6=H VAV
7=C VAV
8=VAV
9=H C VAV
2
RCPSettings.RegioHeatSetPointOccupied
22
°C
Room Base setpoint heating
3
RCPSettings.RegioCoolSetPointOccupied
24
°C
Room Base setpoint cooling
4
RCPSettings.RegioRoomTempPBand
10
Temperature PID P Band
5
RCPSettings.RegioRoomTempITime
300
sec
Temperature PID I Time
6
RCPSettings.RegioHeatSetPointUnoccupied
15
°C
Setpoint heating in Unoccupied
7
RCPSettings.RegioCoolSetPointUnoccupied
30
°C
Setpoint Cooling in Unoccupied
8
RCPSettings.RegioSetPointDeadBandStandby
3
°C
Deadband in Standby mode
9
RCPSettings.RegioFrostProtectionSetPoint
8
°C
Setpoint frostprotection
10
RCPSettings.
RegioSupplyAirTempLimCascadeFactor
3
Cascade Factor for the Cascade PID
11
RCPSettings.RegioSupplyAirTempLimHeatMinLimit
24
°C
Min Setpoint for the Cascade PID in Heat
Mode
12
RCPSettings.RegioSupplyAirTempLimHeatMaxLimit 35
°C
Max Setpoint for the Cascade PID in Heat
Mode
13
RCPSettings.RegioSupplyAirTempLimCoolMinLimit
12
°C
Min Setpoint for the Cascade PID in Cool
Mode
14
RCPSettings.RegioSupplyAirTempLimCoolMaxLimit 24
°C
Max Setpoint for the Cascade PID in Cool
Mode
15
RCPSettings.
RegioSupplyAirTempLimFrostProtSetPoint
8
°C
Supply Air Temp Frost Protection Temperature
16
RCPSettings.RegioCO2PBand
100
CO2 PID P Band
17
RCPSettings.RegioCO2ITime
100
sec
CO2 PID I Time
18
RCPSettings.RegioCO2SetPoint
600
ppm
Setpoint for CO2 PI Controller in PPM
19
RCPSettings.RegioControllerModeZone2
9
Control Mode Room2
0=Heating
1=H Heating
2=H Cooling
3=Cooling
4=Heating/Cooling (change-over)
5=H Heating/Cooling (change-over)
6=H VAV
7=C VAV
8=VAV
9=H C VAV
20
RCPSettings.RegioHeatSetPointOccupiedZone2
22
°C
Room Base setpoint heating Room2
21
RCPSettings.RegioCoolSetPointOccupiedZone2
24
°C
Room Base setpoint cooling Room2
22
RCPSettings.RegioRoomTempPBandZone2
10
Temperature PID P Band Room2
23
RCPSettings.RegioRoomTempITimeZone2
300
sec
Temperature PID I Time Room2
24
RCPSettings.RegioHeatSetPointUnoccupiedZone2
15
°C
Setpoint heating in Unoccupied Room2
Regio
Ardo
manual, Rev. D
79