Signal name
Object name
Instance
number
Writeable Description
RCPSettings.RegioFanSelectZone2 RegioFanSelectZone2
30119
YES
Fan speed Selected Remote/RegioTool
Room2
1=Off
2=Speed1
3=Speed2
4=Speed3
5=Auto
RCPSettings.RegioRUTempUnit
RegioRUTempUnit
30120
YES
Display Unit
1=None
2=°C
3=°F
RCPActual.RegioControlState
RegioControlState
40027
NO
Current unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=ByPass
RCPActual.RegioHeatCoolSymbol
RegioHeatCoolSymbol
40028
NO
Current controller state
1=Off
2=Heating
3=Cooling
4=Heating and Cooling
RCPActual.RegioFanSpeed
RegioFanSpeed
40035
NO
Current 3speed fan speed
1=Off
2=Speed1
3=Speed2
4=Speed3
RCPActual.
RegioFanSpeedSelectCombined
RegioFanSpeedSelect-
Combined
40037
NO
Fan speed Selected
1=Off
2=Speed1
3=Speed2
4=Speed3
5=Auto
RCPActual.RegioMasterSlaveState RegioMasterSlaveState
40039
NO
Current State in Removable Walls Feature
1=StandAlone
2=Master
3=Slave
4=Slave with comm error running as
standalone
RCPActual.
RegioControlStateZone2
RegioControlStateZone2
40055
NO
Current unit state Room2
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=ByPass
RCPActual.
RegioHeatCoolSymbolZone2
RegioHeatCoolSymbol-
Zone2
40056
NO
Current controller state
1=Off
2=Heating
3=Cooling
4=Heating and Cooling
RCPActual.RegioFanSpeedZone2
RegioFanSpeedZone2
40063
NO
Current 3speed fan speed Room2
1=Off
2=Speed1
3=Speed2
4=Speed3
RCPActual.RegioFanSpeedSelect-
CombinedZone2
RegioFanSpeedSelect-
CombinedZone2
40065
NO
Fan speed Selected Room2
1=Off
2=Speed1
3=Speed2
4=Speed3
5=Auto
Regio
Ardo
manual, Rev. D
121