Signal name
Modbus
address
Default
value
Scale
Description
AlaData.AlaPt13_DelayValue
457
0
1
Delay value for point no. 13 Slave3CommFail
AlaData.AlaPt14_DelayValue
458
0
1
Delay value for point no. 14 Slave4CommFail
AlaData.AlaPt15_DelayValue
459
0
1
Delay value for point no. 15 RoomTempHigh
AlaData.AlaPt16_DelayValue
460
0
1
Delay value for point no. 16 RoomTempLow
AlaData.AlaPt17_DelayValue
461
0
1
Delay value for point no. 17 RoomTempDeviation
AlaData.AlaPt18_DelayValue
462
0
1
Delay value for point no. 18
RoomControllerInManualMode
AlaData.AlaPt19_DelayValue
463
0
1
Delay value for point no. 19
RoomTempHighRoom2
AlaData.AlaPt20_DelayValue
464
0
1
Delay value for point no. 20 RoomTempLowRoom2
AlaData.AlaPt21_DelayValue
465
0
1
Delay value for point no. 21
RoomTempDeviationRoom2
AlaData.AlaPt22_DelayValue
466
0
1
Delay value for point no. 22
RoomControllerInManualModeRoom2
AlaData.AlaPt23_DelayValue
467
0
1
Delay value for point no. 23 MasterCommFail
AlaData.AlaPt24_DelayValue
468
0
1
Delay value for point no. 24 SlaveNormalOperation
AlaData.AlaPt25_DelayValue
469
10
1
Delay value for point no. 25 CO2 Level High
AlaData.AlaPt26_DelayValue
470
10
1
Delay value for point no. 26 CO2 Level High
Room2
Alarms.AlaAcknow
471
-
1
External acknowledge command
Alarms.AlaBlock
472
-
1
External blocking command
Alarms.AlaUnBlock
473
-
1
External unblocking command
C.4 Input status registers
Signal name
Modbus
address
Description
RCPActual.RegioOpenWindowInd
1
Open window indication
RCPActual.RegioCondensationAlarm
2
Alarm Condensation indication
RCPActual.RegioPresenceInd
3
Pressens indication
RCPActual.RegioChangeOverInd
4
Change over indication
RCPActual.RegioDigOut1
5
Digital output 1
RCPActual.RegioDigOut2
6
Digital output 2
RCPActual.RegioDigOut3
7
Digital output 3
RCPActual.RegioDigOut4
8
Digital output 4
RCPActual.RegioDigOut5
9
Digital output 5
RCPActual.RegioDigOut6
10
Digital output 6
RCPActual.RegioFanSpeed1Output
11
Start Fan Speed 1
RCPActual.RegioFanSpeed2Output
12
Start Fan Speed 2
RCPActual.RegioFanSpeed3Output
13
Start Fan Speed 3
RCPActual.RegioLightingOutput
14
Start signal Lighting
RCPActual.RegioSunBlindsInOutput
15
In signal Blind
RCPActual.RegioSunBlindsOutOutput
16
Out signal Blind
RCPActual.RegioForcedVentOutput
17
Start forced ventilation
RCPActual.RegioHeat1IncOutput
18
Increase heat 1 valve
Regio
Ardo
manual, Rev. D
115