Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioTempFilterFactorZone2
270
0.2
100
Filter factor for temperature on analog input in
Room2:
0=no filter
1=Max filter
RCPSettings.RegioCondFilterFactorZone2
271
0.2
100
Filter factor for condense on analog input in
Room2:
0=no filter
1=Max filter
RCPSettings.RegioCO2FilterFactorZone2
272
0.2
100
Filter factor for CO2 on analog input in Room2:
0=no filter
1=Max filter
RCPSettings.RegioRHFilterFactorZone2
273
0.2
100
Filter factor for RH on analog input in Room2:
0=no filter
1=Max filter
RCPSettings.RegioInternalTempCompZone2
274
0
10
Internal temperature sensor compensation for
Room2
RCPSettings.RegioHeat1OutputSelect
275
2
1
Manual/Auto of Heat1
0=Off
1=Manual
2=Auto
RCPSettings.RegioHeat2OutputSelect
276
2
10
Manual/Auto of Heat2
RCPSettings.RegioCoolOutputSelect
277
2
1
Manual/Auto of Cool1
RCPSettings.RegioHeatCoolOutputSelect
278
2
1
Manual/Auto of Heat Cool
RCPSettings.RegioVAVOutputSelect
279
2
1
Manual/Auto of VAV
RCPSettings.RegioECFanOutputSelect
280
2
1
Manual/Auto of ECFan
RCPSettings.RegioHeat1OutputSelectZone2
281
2
1
Manual/Auto of Heat1 Room2
RCPSettings.RegioHeat2OutputSelectZone2
282
2
1
Manual/Auto of Heat2 Room2
RCPSettings.RegioCoolOutputSelectZone2
283
2
1
Manual/Auto of Cool1 Room2
RCPSettings.RegioHeatCoolOutputSelectZone2
284
2
1
Manual/Auto of Heat Cool Room2
RCPSettings.RegioVAVOutputSelectZone2
285
2
1
Manual/Auto of VAV Room2
RCPSettings.RegioECFanOutputSelectZone2
286
2
1
Manual/Auto of ECFan Room2
RCPSettings.RegioHeat1OutputManual
287
0
1
Manual value Heat 1
RCPSettings.RegioHeat2OutputManual
288
0
1
Manual value Heat 2
RCPSettings.RegioCoolOutputManual
289
0
1
Manual value Cool
RCPSettings.RegioHeatCoolOutputManual
290
0
1
Manual value Heat Cool
RCPSettings.RegioVAVOutputManual
291
0
1
Manual value VAV
RCPSettings.RegioECFanOutputManual
292
0
1
Manual value ECFan
RCPSettings.RegioHeat1OutputManualZone2
293
0
1
Manual value Heat 1 Room2
RCPSettings.RegioHeat2OutputManualZone2
294
0
1
Manual value Heat 2 Room2
RCPSettings.RegioCoolOutputManualZone2
295
0
1
Manual value Cool Room2
RCPSettings.RegioHeatCoolOutputManualZone2 296
0
1
Manual value Heat Cool Room2
RCPSettings.RegioVAVOutputManualZone2
297
0
1
Manual value VAV Room2
RCPSettings.RegioECFanOutputManualZone2
298
0
1
Manual value ECFan Room2
RCPSettings.RegioLightSelect
299
2
1
Manual/Auto of Lighting:
0=Off
1=On
2=Auto
RCPSettings.RegioSunBlindsInSelect
300
2
1
Manual/Auto of BlindIn
RCPSettings.RegioSunBlindsOutSelect
301
2
1
Manual/Auto of BlindOut
RCPSettings.RegioForcedVentSelect
302
2
1
Manual/Auto of ForceVentilation
RCPSettings.RegioDigOutSelectSumAlarm
303
2
1
Manual/Auto of SumAlarm
Regio
Ardo
manual, Rev. D
109