Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioPropValveHeat2PeriodTime
208
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveCool1PeriodTime
209
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveCool2PeriodTime
210
210
1
Not used
RCPSettings.
RegioPropValveHeatCoolPeriodTime
211
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveVAVPeriodTime
212
210
1
Period time (sec) if puls prop control valves
RCPSettings.RegioPropValveECFanPeriodTime
213
210
1
Period time (sec) if puls prop control valves
RCPSettings.
RegioPropValveHeat1PeriodTimeZone2
214
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.
RegioPropValveHeat2PeriodTimeZone2
215
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.
RegioPropValveCool1PeriodTimeZone2
216
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.
RegioPropValveCool2PeriodTimeZone2
217
210
1
Not used
RCPSettings.
RegioPropValveHeatCoolPeriodTimeZone2
218
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.
RegioPropValveVAVPeriodTimeZone2
219
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.
RegioPropValveECFanPeriodTimeZone2
220
210
1
Period time (sec) if puls prop control valves Room2
RCPSettings.RegioCVHeatExerciseDay
221
8
1
Day for exercise heating and heat/cool valve:
0=Never
1-7=mon-sun
8=every day
RCPSettings.RegioCVCoolExerciseDay
222
8
1
Day for exercise cooling valve:
0=Never
1-7=mon-sun
8=every day
RCPSettings.RegioCVHeatExerciseHour
223
15
1
Hour for exercise heating and heat/cool valve
RCPSettings.RegioCVCoolExerciseHour
224
15
1
Hour for exercise cooling valve
RCPSettings.RegioCVHeatExerciseMin
225
0
1
Minute for exercise heating valve
RCPSettings.RegioCVCoolExerciseMin
226
0
1
Minute for exercise cooling valve
RCPSettings.RegioHeatExerciseTime
227
120
1
Time in seconds to Exercise the Heat Valves
RCPSettings.RegioCoolExerciseTime
228
120
1
Time in seconds to Exercise the Cool Valves
RCPSettings.
RegioSixWayValveFirstSeqFullyOpen
229
0
10
6 Way valve tension (V) for fully open on 1st
sequence
RCPSettings.
RegioSixWayValveFirstSeqStartOpen
230
3.3
10
6 Way valve tension (V) for start open on 1st
sequence
RCPSettings.
RegioSixWayValveSecondSeqStartOpen
231
6.7
10
6 Way valve tension (V) for start open on 2nd
sequence
RCPSettings.
RegioSixWayValveSecondSeqFullyOpen
232
10
10
6 Way valve tension (V) for fully open on 2nd
sequence
RCPSettings.RegioSixWayValveCenterPoint
233
5
10
6 Way valve tension (V) for center point
RCPSettings.RegioSixWayValveCenterPointHyst
234
2
1
6 Way valve centerpoint hysteresis (%)
RCPSettings.RegioCVHeatExerciseDayZone2
235
8
1
Day for exercise heating valve Room2:
0=Never
1-7=mon-sun
8=every day
RCPSettings.RegioCVCoolExerciseDayZone2
236
8
1
Day for exercise cooling valve Room2:
0=Never
1-7=mon-sun
8=every day
Regio
Ardo
manual, Rev. D
107