Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioDo1
159
7
1
Configuration for Digital Output 1
0 =Disabled
1 =Fan speed 1
2 =Fan speed 2
3 =Fan speed 3
4 =Lighting
5 =Blind in
6 =Blind out
7 =Forced ventilation
8 =Heat valve Inc.
9 =Heat valve Dec
10=Heat valve thermal(PWM)
11=Heat valve 2 Inc.
12=Heat valve 2 Dec.
13=Heat valve 2 thermal(PWM)
14=Cool valve Inc.
15=Cool valve Dec.
16=Cool valve thermal(PWM)
17=Not used
18=Not used
19=Not used
20=Change over valve Inc
21=Change over valve Dec
22=Change over thermal(PWM)
23=SumAlarm
24=SumAlarm A
25=SumAlarm B
101=Fan speed 1 room 2
102=Fan speed 2 room 2
103=Fan speed 3 room 2
104=Lighting room 2
105=Blind in room 2
106=Blind out Room 2
107=Forced ventilation room 2
108=Heat Valve Inc.room 2
109=Heat Valve Dec room 2
110=Heat Valve thermal(PWM) room 2
111=Heat Valve 2 Inc. room 2
112=Heat Valve 2 Dec. room 2
113=Heat Valve 2 Thermal(PWM) room 2
114=Cool Valve Inc. room 2
115=Cool Valve Dec. room 2
116=Cool Valve thermal(PWM) room 2
117=Not used
118=Not used
119=Not used
120=Change over Valve Inc. room 2
121=Change over Valve Dec. room 2
122=Change over Thermal(PWM) room 2
123=SumAlarm room 2
124=SumAlarm A room 2
125=SumAlarm B room 2
RCPSettings.RegioDo2
160
23
1
Configuration for Digital Output 2
RCPSettings.RegioDo3
161
0
1
Configuration for Digital Output 3
RCPSettings.RegioDo4
162
0
1
Configuration for Digital Output 4
RCPSettings.RegioDo5
163
0
1
Configuration for Digital Output 5
RCPSettings.RegioDo6
164
0
1
Configuration for Digital Output 6
RCPSettings.RegioHeatValve1Type
165
0
1
Output Signal for HeatValve1:
0=0-10V
1=2-10V
2=10-2V
3=10-0V
4=Inc/Dec
5=PWM(Thermal)
6=6 Way-vay valve
RCPSettings.RegioHeatValve2Type
166
0
1
Output Signal for HeatValve2:
Regio
Ardo
manual, Rev. D
105