Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioFanAfterBlowControlZone2
133
0
1
If enabled the Fan will work FanStopTime after
Heat applied:
0=Off
1=Heat1
2=Heat2
3=Heat1 or Heat2
RCPSettings.RegioFanAfterBlowMinSpeedZone2 134
0
1
Minimum Fan Speed when FanafterBlow Active
RCPSettings.RegioKickStartTimeZone2
135
0
1
Time (Sec) to Kick Start the Fan for Room2, during
this time the fan will work at 100%. If 0 this function
is not active
RCPSettings.RegioBoostModeZone2
136
2
1
Boost Function will work when on Room2:
0=Heating
1=Cooling
2=Both
RCPSettings.RegioConfigFanBoostTimeZone2
137
0
1
Time (sec) [0 to 600 seconds] that the Boost Func-
tion is active. If 0 the boost function is disabled
Room2
RCPSettings.RegioShortStartZone2
138
10
1
Time (sec) that the Fan runs in Max Speed Room2
RCPSettings.RegioBoostPBandZone2
139
5
1
P-band of the P-Controller of the Fan (just in Boost
Startup Mode) Room2
RCPSettings.RegioLightControlFunctionZone2
140
0
1
Select light control function Room2:
0=Central controlled,
1=Local Time controlled
2=Presence controlled
3=Time or Presence controlled
4=Central controlled or Presence controlled
RCPSettings.RegioSunBlindsRunTimeZone2
141
240
1
Run time for controlling the jalusi in/out (sec)
Room2
RCPSettings.RegioSunBlindsControlZone2
142
0
1
Remote Control for the Jalusi Room2
0=Go In
1=Stop
2=Go out
RCPSettings.RegioAi1
143
0
1
Configuration for Analog Input 1
0=Disable
1=External room temp
2=ChangeOver temp
3=Outdoor temp
4=Condensation
5=CO2 sensor
6=RH sensor
7=Not used
8=Not used
9=Not used
11=Supply air Temp
101=External room temp room 2
102=Not used
103=Outdoor temp room 2
104=Condensation room 2
105=CO2 sensor room 2
106=RH sensor room 2
107=Not used
108=Not used
109=Not used
111=Supply air temp room 2
RCPSettings.RegioAi2
144
0
1
Configuration for Analog Input 2
RCPSettings.RegioAi3
145
0
1
Configuration for Analog Input 3
RCPSettings.RegioAi4
146
0
1
Configuration for Analog Input 4
Regio
Ardo
manual, Rev. D
103