Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioForcedVentControlModeZone2 107
3
1
Forced Ventilation Control Mode Room2:
0=Off
1=Force Vent on Heat
2=Force Vent on Cool
3=Force Vent on Both Heat and Cool
RCPSettings.
RegioForcedVentAtMaxOutputZone2
108
0
1
Forced Ventilation on Max Heat/Cool/Both Room2:
0=Off
1=Forced Ventilation on Max Heat
2=Forced Ventilation on Max Cool
3=Forced Ventilation on Max Heat or Cool
RCPSettings.RegioVAVControlType
109
2
1
Control the VAV output:
0=By temperature
2=By CO2 level
3=By both, the highest need
RCPSettings.RegioVAVControlTypeZone2
110
2
1
Control the VAVoutput Room2:
0=By temperature
2=By CO2 level
3=By both, the highest need
RCPSettings.
RegioSupplyAirTempLimCascadeFactorZone2
111
3
1
Cascade Factor for the Cascade PID Room2
RCPSettings.
RegioSupplyAirTempLimHeatMinLimitZone2
112
24
1
Min Setpoint for the Cascade PID in Heat Mode
Room2
RCPSettings.
RegioSupplyAirTempLimHeatMaxLimitZone2
113
35
1
Max Setpoint for the Cascade PID in Heat Mode
Room2
RCPSettings.
RegioSupplyAirTempLimCoolMinLimitZone2
114
12
1
Min Setpoint for the Cascade PID in Cool Mode
Room2
RCPSettings.
RegioSupplyAirTempLimCoolMaxLimitZone2
115
24
1
Max Setpoint for the Cascade PID in Cool Mode
Room2
RCPSettings.
RegioSupplyAirTempLimFrostProtSetPointZone2
116
8
1
Supply Air Temp Frost Protection Temperature
Room2
RCPSettings.RegioCO2PBandZone2
117
100
1
CO2 PID P Gain Room2
RCPSettings.RegioCO2ITimeZone2
118
100
1
CO2 PID I Time Room2
RCPSettings.RegioCO2SetpointZone2
119
600
1
Setpoint for CO2 PI Controller in PPM Room2
RCPSettings.RegioCO2PresenceLimitZone2
120
800
1
Activate presence if CO2 is higher Room2
RCPSettings.RegioCO2PresenceHystZone2
121
160
1
Diff for deactivate presence on CO2 Room2
RCPSettings.RegioFanControlModeZone2
122
0
1
FanControl Mode Room2:
0=No control
1=Controlled by Heating
2=Controlled by cooling
3=Controlled by both heat and cooling
RCPSettings.RegioFanSpeed1StartZone2
123
20
1
If higher controller output start fanspeed 1 Room2
RCPSettings.RegioFanSpeed2StartZone2
124
60
1
If higher controller output start fanspeed 2 Room2
RCPSettings.RegioFanSpeed3StartZone2
125
100
1
If higher controller output start fanspeed 3 Room2
RCPSettings.RegioFanSpeedHystZone2
126
5
1
Hysteresis % for start/stop fan Room2
RCPSettings.RegioRUNoOfFanSpeedsZone2
127
3
1
Configured number of fanspeeds (1-3) Room2
RCPSettings.RegioFanSwitchTimeZone2
128
2
1
Time (sec) before switching fan speed when
changed from RU Room2
RCPSettings.RegioECFanMaxLimitZone2
129
100
1
Max limit for the EC fan (0-100) Room2
RCPSettings.RegioECFanMinLimitZone2
130
10
1
Min limit for the EC fan (0-100) Room2
RCPSettings.RegioECFanStartSpeedZone2
131
15
1
Only will output values above this Speed Room2
RCPSettings.RegioFanStopTimeZone2
132
120
1
Time (Sec) for the Fan Stop delay when Fan After-
Blow used