Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.
RegioCoolSetPointUnoccupiedZone2
79
30
10
Setpoint Cooling in Unoccupied Room2
RCPSettings.
RegioSetPointDeadBandStandbyZone2
80
3
10
Deadband in Standby mode Room2
RCPSettings.RegioFrostProtectionSetPointZone2 81
8
10
Setpoint frostprotection Room2
RCPSettings.RegioRUSetPointAdjPosZone2
82
3
1
Max allowed offset over setpoint Room2
RCPSettings.RegioRUSetPointAdjNegZone2
83
3
1
Max allowed offset below setpoint Room2
RCPSettings.RegioSetPOffsetZone2
84
0
10
Setpoint Offset Room2
RCPSettings.RegioSetPOffsetRemoteZone2
85
0
10
Remote Setpoint Offset Room2
RCPSettings.RegioControllerStateReturnZone2
86
3
1
Select return unit state Room2:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
RCPSettings.
RegioControllerStateShutDownZone2
87
1
1
Select shutdown state Room2:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
RCPSettings.
RegioControllerStatePresenceZone2
88
4
1
Presence operating mode Room2:
3=Occupied
4=ByPass
RCPSettings.RegioControllerStateRemoteZone2
89
5
1
Is used for remote control Room2:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No remote control
RCPSettings.
RegioControllerStateBypassTimeZone2
90
120
1
Time for Bypass mode (Min) Room2
RCPSettings.RegioPresenceOffDelayZone2
91
10
1
Off timer for changing to not presence (min) Room2
RCPSettings.RegioPresenceOnDelayZone2
92
0
1
On timer for changing to presence (min) Room2
RCPSettings.RegioHeatOutputMinLimitZone2
93
0
1
Min Limit for Heat Output Room2
RCPSettings.RegioHeatOutputMaxLimitZone2
94
100
1
Max Limit for Heat Output Room2
RCPSettings.RegioHeat2OutputMinLimitZone2
95
0
1
Min Limit for Heat Output Room2
RCPSettings.RegioHeat2OutputMaxLimitZone2
96
100
1
Max Limit for Heat Output Room2
RCPSettings.RegioCool1OutputMinLimitZone2
97
0
1
Min Limit for Cool Output Room2
RCPSettings.RegioCool1OutputMaxLimitZone2
98
100
1
Max Limit for Cool Output Room2
RCPSettings.RegioCool2OutputMinLimitZone2
99
0
1
Not used
RCPSettings.RegioCool2OutputMaxLimitZone2
100
100
1
Not used
RCPSettings.RegioVAVOutputMinLimitOffZone2
101
0
1
Min Limit for VAV Output at off State Room2
RCPSettings.RegioVAVOutputMinLimitUnoZone2
102
10
1
Min Limit for VAV Output at Unoccupied State
Room2
RCPSettings.
RegioVAVOutputMinLimitStandbyZone2
103
10
1
Min Limit for VAV Output at Standby State Room2
RCPSettings.RegioVAVOutputMinLimitOccZone2
104
20
1
Min Limit for VAV Output at Occupied or Bypass
State Room2
RCPSettings.RegioVAVOutputMaxLimitZone2
105
100
1
Max Limit for VAV Output Room2
RCPSettings.RegioMaxAirflowHeatDemandZone2 106
0
1
Max Airflow on Heat Demand , if above 0% the max
ariflow function is enabled Room2