Page 1: ...en WE TAKE BUILDING AUTOMATION PERSONALLY VARIABLE LIST RDAS 24C...
Page 2: ...rket as well as of how our products and systems function under the most variable conditions Every year Regin makes substantial investments in the development of our systems and HVAC products DISCLAIME...
Page 3: ...Human machine interface RDAS5 24C and RDAS10 24C 8 3 1 1 Push button operation 8 3 1 2 LED colors and patters 8 3 1 3 Reset by push button 9 3 2 HMI Human machine interface RDAS7S 24C RDAS18S 24C RDA...
Page 4: ......
Page 5: ...tion Torque Max damper size Sound power level RDAS5 24C 24 V AC 20 28 V AC 50 60 Hz 3VA 2 5 W 150s 90 5 Nm 0 8 m2 28 dB RDAS10 24C 24 V AC 20 28 V AC 50 60 Hz 3VA 2 5 W 150s 90 10 Nm 1 6 m2 28 dB RDAS...
Page 6: ...requirements Additionally ensure that the dampers are shut tight when in the fully closed position Fasten the actuator securely to avoid side load Check the rotary movement Manually set the damper by...
Page 7: ...Comissioning notes Figure 2 1 Clockwise RDAS 24C variable list Rev A 7...
Page 8: ...3 1 Display current address starting with lowest address digit Enter Modbus address with push button Press and hold button between 1 and 5 seconds See description in section 3 3 Push button addressing...
Page 9: ...celled 4 After these 3 seconds LED shines red reset then green start up See section 3 3 Push button addressing for more information and examples 3 2 HMI Human machine interface RDAS7S 24C RDAS18S 24C...
Page 10: ...life pulse without bus traffic flashing Normal operation life pulse with bus traffic Orange green 1 second orange 1 second green Device is in override control Orange 1 second on 1 second off Bus param...
Page 11: ...D shines red confirmation release button An address can be stored at any time i e after setting the 1 digits or after setting the 1 and the 10 digits 5 Entered address is repeated one times for confir...
Page 12: ...ED flashes red per button press 3 Store address skip 10 digit and 100 digit Press button until LED shines red address is stored and displayed 1 time for confirmation Figure 3 5 Example address 5 3 4 C...
Page 13: ...s to 246 with push button press and hold between 5 and 10 seconds After addressing all devices the remaining configuration can be done over the bus using the default settings for bauderate auto baud a...
Page 14: ...Timeout RW s 1 0 65535 516 Startup Setpoint RW 0 01 0 100 764 Modbus Address RW 1 247 255 unassigned 765 Baudrate RW 0 auto 1 9600 2 19200 3 38400 4 57600 5 76800 6 115200 766 Transmission Format RW 0...
Page 15: ...er and function description Function Reg Description Override control 2 The actuator can be operated in override control for commissioning maintenance purposes or system wide functions e g night cooli...
Page 16: ...initialization reset behaviour Local reset by push button Remote reset Using RemoteFactoryReset command Effect of reset Process values set to default values Parameters Application and actuator paramet...
Page 17: ...RDAS 24C variable list Rev A 17...
Page 18: ...Regin All rights reserved HEAD OFFICE AB Regin Box 116 SE 428 22 K llered Visiting address Bang rdsv gen 35 SE 428 36 K llered Phone 46 0 31 720 02 00 Fax 46 0 31 720 02 50 info regincontrols com www...